3.5 Configuration of the controller
Fully programmable charge algorithm (see the software page on
our website) and eight preprogrammed charge algorithms,
selectable with a rotary switch:
Pos
Suggested battery type
Gel Victron long life (OPzV)
0
Gel exide A600 (OPzV)
Gel MK
Gel Victron deep discharge
Gel Exide A200
1
AGM Victron deep discharge
Stationary tubular plate
(OPzS)
Default setting
Gel Victron deep discharge
2
Gel Exide A200
AGM Victron deep discharge
Stationary tubular plate
(OPzS)
AGM spiral cell
3
Stationary tubular plate
(OPzS)
Rolls AGM
PzS tubular plate traction
4
batteries or
OPzS batteries
PzS tubular plate traction
5
batteries or
OPzS batteries
PzS tubular plate traction
6
batteries or
OPzS batteries
Lithium Iron Phosphate
7
(LiFePo
) batteries
4
Note 1: divide all values by two in case of a 12V system.
Note 2: equalize normally off, see sect. 3.8.1 to activate
(do not equalize VRLA Gel and AGM batteries)
Note 3: any setting change performed with Bluetooth or via VE.Direct will
override the rotary switch setting. Turning the rotary switch will override prior
settings made with Bluetooth or VE.Direct.
Absorption
7
Float
Equalize
V
V
@%I
28,2
27,6
@8%
28,6
27,6
@8%
28,8
27,6
@8%
29,4
27,6
@8%
29,8
27,6
@25%
30,2
27,6
@25%
30,6
27,6
@25%
28,4
27,0
dV/dT
V
mV/°C
nom
31,8
-32
32,2
-32
32,4
-32
33,0
-32
33,4
-32
33,8
-32
34,2
-32
n.a.
0