Ecor Pro EPD150 Manuel page 7

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

US
POSITIONING
|
The EPD dehumidifier is designed only for indoor use however, it can be placed inside or outside the room to
be dried.
INTERNAL POSITIONING
When positioning the unit inside the room, place it centrally, ensuring inlet and outlet ducts are clear of
obstruction.
If required, ducts can be connected to the outlet and/or inlet to direct the drying to specific areas.
The Wet-Air-Out MUST be ducted outside the room
EXTERNAL POSITIONING
When positioning the unit outside the room, connect ducting to the outlet to direct the dry air stream into the
room to be dried.
Optionally, the inlet may also be ducted to the room to give a re-circulation effect. In this case however,
because the unit uses a portion for the inlet air for regeneration, provision must be made in the inlet duct to
also draw air form outside the room.
Note:
As the Wet-Air-Out discharge is warm and very humid ensure it is directed where it will have no adverse
effect on the immediate environment.
All ducting lengths should be kept to a minimum —longer lengths will reduce performance.
The Wet-Air-Out is warm and very humid, when a duct is attached, condensation may form on the inside of
the duct. This duct should slope downwards away may from the unit to prevent any condensation running
back into the unit.
7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Epd200-proEpd150-proEpd200

Table des Matières