TOP
SIDES
BURNER END
DISCHARGE END
VENT CONNECTOR
COMBUSTIBLE FLOOR
FLUE PIPE CONNECTIONS
VENT TO OUTDOORS
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at
least two feet long. Horizontal runs should have rise ratio of 1 in 10 away from the heater. Where
down drafts are liable to occur a vent cap should be used. All venting should correspond with the
CSA B139 standard or local codes.
CAUTION: HEATER FLUE TEMPERATURES CAN REACH 900 °F TO 1000 °F THEREFORE IT
IS A RANGE THAT IS BOTH HAZARDOUS TO HUMANS AND HIGHER THAN THE AUTO-
IGNITION TEMPERATURES OF MANY MATERIALS. THEREFORE EXERCISE CAUTION IN
HEATER PLACEMENT AND THE USE OF AN INSULATED GUARD AND STACK IS HIGHLY
RECOMMENDED.
Horizontal venting runs shall always terminate with a minimum 24" vertical.
NOTE: FOR OPTIMAL COMBUSTION PERFORMANCE A 30" C-VENT FLUE EXTENSION WITH
RAIN CAP IS RECOMMENDED AT ALL TIMES.
Recommended chimney draft - .05 inches of water column
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
1-800-486-4328
1-204-633-1999
NOTE: Installation clearances are as follows:
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
100 Eagle Drive
Winnipeg, MB Canada
3 feet
3 feet
3 feet
10 feet
3 Feet
6 feet
www.campoequipment.com