BLAZE 600 D TURBO Manuel D'installation page 11

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

TOP
SIDES
BURNER END
DISCHARGE END
VENT CONNECTOR
COMBUSTIBLE FLOOR
FLUE PIPE CONNECTIONS
VENT TO OUTDOORS
FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY
When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at
least two feet long. Horizontal runs should have rise ratio of 1 in 10 away from the heater. Where
down drafts are liable to occur a vent cap should be used. All venting should correspond with the
CSA B139 standard or local codes.
CAUTION: HEATER FLUE TEMPERATURES CAN REACH 900 °F TO 1000 °F THEREFORE IT
IS A RANGE THAT IS BOTH HAZARDOUS TO HUMANS AND HIGHER THAN THE AUTO-
IGNITION TEMPERATURES OF MANY MATERIALS. THEREFORE EXERCISE CAUTION IN
HEATER PLACEMENT AND THE USE OF AN INSULATED GUARD AND STACK IS HIGHLY
RECOMMENDED.
Horizontal venting runs shall always terminate with a minimum 24" vertical.
NOTE: FOR OPTIMAL COMBUSTION PERFORMANCE A 30" C-VENT FLUE EXTENSION WITH
RAIN CAP IS RECOMMENDED AT ALL TIMES.
Recommended chimney draft - .05 inches of water column
Tel: (905) 793-2525 | Fax: (905) 793-8768 |
1-800-486-4328
1-204-633-1999
NOTE: Installation clearances are as follows:
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
100 Eagle Drive
Winnipeg, MB Canada
3 feet
3 feet
3 feet
10 feet
3 Feet
6 feet
www.campoequipment.com
P a g e
sales@hermannelson.com
www.hermannelson.com
| 11