G
TAKE CARE
For the SC33xx models: The length of the piping is 4 metres.
For the S33xx models: The maximum length of the piping between the interior and exterior unit
More than 15 cm.
More than 12 cm.
5.2 Determining the location of the exterior unit for the S33xx en SC33xx
models
•
Install the outdoor unit on a rigid base to prevent increasing noise level and vibration.
G
NOTE
The outdoor unit produces sound when in use, this could interfere with local legislation. It
is the responsibility of the user to check and to make sure the equipment is in full compliance
with local legislation.
•
Determine the air outlet direction where the drainaged air is not blocked.
•
Take the air conditioner weight into account.
•
If an awning is built over the outdoor unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
•
Ensure that the clearance around the back of the unit is more than 30 cm and left side is more than 30
cm. The front of the unit should have more than 200 cm of clearance and the connection side (right
side) should have more than 60 cm of clearance. See picture 5.
•
Be sure to level the outdoor unit
LEFT
More than 30 cm.
FRONT
More than 200 cm.
is 20 metres.
The maximum difference in height between the interior and exterior unit is
8 metres.
More than 12 cm.
2.3 m or more
More than 60 cm.
More than 30 cm.
More than 60 cm.
Figure 4
BACK
RIGHT
4
49
49