INSTALLATION continued
Less than 10 feet (3 meters)
2' (60cm)
Min.
Termination Less than 10 feet (3 meters) from ridge
Testing & Lighting Instructions
1. Turn on main gas valve. Remove the lower front cover
and the service panel above the control panel. Drop the
control panel and leak test all fi ttings and connections
upstream from the service valve located on the redundant
combination gas valve. Should any gas leaks be detected,
turn OFF main gas valve, correct the problem and retest.
2. Open shutoff valve located on the redundant combination
gas valve. Activate control panel and set to desired
temperature. The main burners are ignited by direct spark.
Check all fi ttings again and correct any leaks and recheck.
Replace all service panels and covers before operation.
NOTE: All electronic ignition systems are supplied with a
redundant gas valve. Therefore, the unit is not supplied with
an external pressure regulator.
10
3' (90cm) Min.
Termination More than 10 feet (3 meters) from ridge
NOTE: During installation there will be air in the gas line. This
air will have to bleed off before ignition can be established.
The electronic ignition system has 3 cycles of four second
ignition attempts before the ignition module is "Locked Out".
There is a fi ve minutes interval between each attempt. This is
a safety device on all units. Therefore, several attempts may
be required before the ignition is established.
If the ignition module becomes, "Locked Out" the oven will
need to be turned off and then back on to restart the ignition
process again.
FOR YOUR SAFETY: KEEP YOUR APPLIANCE AREA FREE FROM
Do not waste energy by leaving controls at high temperature
settings during idle periods. Lower settings will keep oven
warm and ready for next use period.
More than 10' (3 meters)
COMBUSTIBLES.
TO CONSERVE ENERGY:
Part Number 260BGS rev B 4/15
3' (90cm) Min.