SECTION 2 |
3 Stages of charging for 100% return of capacity and long battery life – Bulk, Absorp-
tion and Float Stages
Can safely charge 2 types of Lead Acid batteries – Flooded / Wet Cell (Absorption Volt-
age 14.8V) or Sealed AGM (Absorption Voltage 14.5V)
Very low self consumption of < 9 mA
MOSFET based reverse current blocking for night-time battery discharge prevention.
This allows much lower losses as compared to Diode based blocking
Totally sealed and splash proof design with Ingress Protection Rating of IP65. Can be
installed in outdoor locations
Wide operating temperature range of -40°C to +60°C
Automatically turns on the loads (like lights) when dark and turns off at day time.
Ideal for street lights / automatic night lighting
Low voltage disconnect protects the battery against deep discharge when the load is
connected to the Load Terminals.
Protected against overload, over temperature, under / over voltage on the battery side
and reverse polarity (see Specifications)
EMC compliance to FCC Standard Part 15(B) for Class B Devices and European Standard
EN61000
Industry leading warranty of 5 years.
2.3 PWM BATTERY CHARGING ALGORITHM USED IN SCC-1208L
Please read Section 3 for supplementary information on PWM charging control.
Fig. 2.1 represents the 3 stages of charging used in SCC-1208L. The charging is carried out
in 3 stages:
Voltage
Description & Principles of Operation
14.8V ± 0.2V for flooded Battery, or
14.5V ± 0.2V for sealed AGM Battery
BULK
ABSORPTION
Fig. 2.1 Solar Charging Stages
13.8V ± 0.2V at 25°C
FLOAT
SAMLEX AMERICA INC. | 5
Time