Vertical Termination - Napoleon Arlington GDS20PSB Manuel D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

venting
EN
2.7

vertical termination

Simple venting configurations.
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
< V
T
T
Formula 2: H
+ V
< 40 feet (12.2m)
T
T
Example:
V
= 5 FT (1.5m)
1
V
= 10 FT (3.1m)
2
V
= V
+ V
= 5 FT (1.5m) + 10 FT (3.1m) = 15 FT (4.6m)
T
1
2
H
= 3 FT (0.9m)
1
H
= 2.5 FT (0.8m)
2
H
= H
+ H
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
R
1
2
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
+ H
= 5.5 FT (1.7m)+ 5.4 FT (1.m) = 10.9 FT (3.3m)
T
R
O
H
+ V
= 10.9 FT (3.3m)+ 15 FT (4.6m) = 25.9 FT (7.9m)
T
T
Formula 1:
H
T
10.9FT (3.3m) < 15 (4.6m)
Formula 2:
H
T
25.9FT (7.9m) < 40 (12.2m)
Since both formulas are met, this vent configuration is acceptable.
16
W415-2345 / B / 12.09.19
VERTICAL RISE
< V
T
+ V
< 40 FT (12.2m)
T
(H
) < (V
)
T
T
See graph to determine the required vertical rise V
required horizontal run H
40 (12.2)
30 (9.1)
REQUIRED
20 (6.1)
IN FEET
(METERS) V
T
10 (3.1)
3 (0.9)
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
45°
T
.
T
5
10 (3.1)
20
15
(1.5)
(6.1)
(4.6)
values for H
and V
T
T
90°
H
2
V
1
H
1
90°
for the
T
V
2
90°