SE
Felsökning
NO
Feilsøking
FI
Vianetsintä
NL
Storingzoeken
Fault
No water comes out when tap is
activated.
Tap does not turn off.
The tap starts running without
being turned on.
The tap drips.
The sensor is flashing.
The temperature is not correct.
The pressure is too high/low.
The programme cannot be
changed.
EN
DK
DE
FR
Possible cause
Supply voltage is too low.
Blocked inlet screens.
Defective/blocked solenoid valve.
The mixer may be in hygiene flush
mode.
Faulty solenoid valve.
Flush time may be set too high.
Hygiene flush mode may be
activated.
Leaking solenoid valve.
Supply voltage is too low.
Incorrect water pressure and
temperature.
The aerator is blocked.
The filters (inlet/solenoid valve) are
blocked.
The tap is locked by the remote
control.
The tap needs to be activated im-
mediately before programming.
39(45)
Troubleshooting guide
Fejlsøgning
Fehlersuche
Dépannage
Action
Check battery/voltage.
Clean the inlet screens.
Replace the solenoid valve.
Wait three to thirty minutes or
briefly switch off the power. (Yellow
LED flashes in flush mode).
Replace the solenoid valve.
Wait up to thirty seconds or
briefly switch off the power. Reset
the sensor.
(Yellow LED flashes in hygiene
flush mode).
Replace the solenoid valve.
Check battery/voltage.
Set the temperature value on its
coldest/hottest setting and check
that the water pressure and tem--
perature are high enough.
Clean the aerator.
Clean the inlet screens and
replace the solenoid valve if
necessary.
Programme seven is activated.
Use the remote control to change
the programme.
Activate it by hand before pro--
gramming.