Function; Operation And Operating Modes; Parameterization / Nominal Current Setting - Phoenix Contact ELR W3-24DC/500AC-2I Manuel D'instructions

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Function

4.1. Operation and operating modes

4.1.1. Status LEDs
The solid-state reversing contactor displays
the operating conditions with a total of four
LEDs. The functions of the LEDs are based
on the NAMUR recommendation NE 44.
After the rated control supply voltage is
applied, all LEDs light up once as LED test.
The operating status of the relay is display-
ed via a green LED.
An external error (process error: overcur-
rent, asymmetry, phase failure) is signaled
by a red LED. The device is currently in a
secure deactivated state. An error acknow-
ledgment is required to exit this state.
The reverse or forward running of the drive
is always displayed by a yellow LED.
4.2. Parameterization /
Nominal current setting
• Activate the reset button for more than 6 s to
reach the operating mode "Parameterization" -
the green LED PWR flashes once.
The LEDs are switched off at intervals of 2 s for 0.3 s
in the operating mode "Parameterization" to diffe-
rentiate from other operating conditions.
• Set the rated current of the drive with the 240°
potentiometer. The four LEDs display the set
current. The rated current is displayed in 16
stages.
• Store the value by pressing the reset button again
(retentive area of the memory).
• Actuate the Reset key for more than 2 s (and less
than 6 s) to display the set current for 3 s.
This function is possible only if
1) the device is not activated, and
2) there is no defect in the device.
Overload current factor:
The ratio between the actual current and the
parameterized rated current.
From a motor current of 12 A or 45 A, the
blocking monitor is activated
(refer to 6.1. Tripping characteristics).
"PWR" LED
Device status
(green)
OFF
No supply voltage
(rated control supply voltage)
ON
Supply voltage (rated control supply
voltage) present
"ERR" LED
Device and process errors
(red)
OFF
No error
Continuously on Internal device errors
Flashing
Error in the control or peripherals.
(Maintenance requirement, NE 44,
refer to chapter "Error Detection")
LED L (yellow)
Process messages
LED R (yellow)
OFF
No message present
Continuously on Drive activated:
reverse running (L) or forward running (R)
Code
PWR ERR L R
0
0
0 0
0
0
0 1
0
0
1 0
0
0
1 1
0
1
0 0
0
1
0 1
0
1
1 0
0
1
1 1
1
0
0 0
1
0
0 1
1
0
1 0
1
0
1 1
1
1
0 0
1
1
0 1
1
1
1 0
1
1
1 1
Nominal
Nominal
current
current
2 A version
9 A version
[mA]
[mA]
180
1500
250
2000
410
2500
560
3000
710
3500
870
4000
1020
4500
1170
5000
1330
5500
1480
6000
1630
6500
1790
7000
1940
7500
2090
8000
2250
8500
2400
9000
19

Publicité

Table des Matières
loading

Table des Matières