Mitsubishi Electric PUMY-P36 Manuel D'installation page 5

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2. Installation location
Fig. 2-5
Fig. 2-9
Fig. 2-12
Fig. 2-15
Minimum dimensions are as follows, except for Max., meaning Maximum dimen-
sions, indicated.
1 Obstacles at rear (Fig. 2-5)
2 Obstacles at rear and above (Fig. 2-6)
3 Obstacles at rear and sides (Fig. 2-7)
4 Obstacles at front (Fig. 2-8)
* When using the optional air outlet guides, the clearance is 19-11/16" (500 mm) or more.
5 Obstacles at front and rear (Fig. 2-9)
* When using the optional air outlet guides, the clearance is 19-11/16" (500 mm) or more.
6 Obstacles at rear, sides, and above (Fig. 2-10)
Fig. 2-6
Fig. 2-10
Fig. 2-13
Fig. 2-16
Leave 1" (25 mm) space or more between the units.
1 Obstacles at rear (Fig. 2-11)
2 Obstacles at rear and above (Fig. 2-12)
3 Obstacles at front (Fig. 2-13)
* When using the optional air outlet guides, the clearance is 39-3/8" (1000 mm) or more.
4 Obstacles at front and rear (Fig. 2-14)
* When using the optional air outlet guides, the clearance is 39-3/8" (1000 mm) or more.
5 Single parallel unit arrangement (Fig. 2-15)
6 Multiple parallel unit arrangement (Fig. 2-16)
7 Stacked unit arrangement (Fig. 2-17)
Fig. 2-7
(1000 mm) or more.
(1500 mm) or more.
shown.
(inch)
Fig. 2-8
Fig. 2-11
Fig. 2-14
Fig. 2-17
5