SOMFY animeo Connect Notice D'installation page 7

Masquer les pouces Voir aussi pour animeo Connect:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 9
EN
A
MOUNTING
[1] Wall mounted
[2] Din-rail mounted
[3] To remove the device from the DIN rail, press the flap
on the back of the device towards the housing and
simultaneously push the housing upwards
B
WIRING
Complete the wiring and connect 24 V power supply.
Power supply needs to provide up to 24 V DC 900 mA to
RS485 bus.
[1] Wiring diagram
A. IP Bus (input/output)
The cable used for the IP Ethernet connection must
be a shielded cable. The shield needs to be connect-
ed on both ends.
Not compatible with PoE switch.
n
B. 7 minutes after switching on the device, the green
flashing LED indicates normal operation.
CHARACTERISTICS
Supply voltage
Power Supply
Minimum current
Max. current
Minimum power
Supply voltage of sensor bus/output
Operating temperature
Relative humidity
Material of housing
Housing dimensions (w x h x d)
Protection class
Degree of protection
Conformity
CABLE
Connection to ...
Power Supply
Ethernet
RS485 Bus
Power Supply (bus)
We care about our environment. Do not dispose of the appliance with usual household waste. Give it to an approved collection point for recycling.
7/20
- animeo Connect . IP Sensor Gateway . Ref. 5137983C
24 V DC +/- 10 % SELV/1 A max.
Mandatory use of certified power supply with limited power (certified according to the relevant
version of 60950-1 or 62368-1, EN/IEC or UL as needed in the country of use).
Limited power classified as LPS, PS2 or UL class II (according to standard)
32 mA
1 A@24 V
0.77 W
24 V DC +/- 10 %
0 ° C ... + 50 ° C
85 % at 30 ° C
ABS
133 x 86 x 44 mm
IP20
www.somfy.com/ce
Cable
Cat. 6
Min.: 2 x 0.3 mm
/22 AWG / Max.: 2 x 0.5 mm
2
Min.: 2 x 0.3 mm
/22 AWG / Max.: 2 x 0.5 mm
2
[2] At the beginning and at the end of the 2-wired RS485
network a 120 Ohm resistance is essential.
m Terminator must not be removed unless a second
weather station is connected.
m Do not connect more than 2 weather stations to the
gateway. Take care of the consumption.
C
COMMISSIONING AND OPERATING
Complete installation of all devices and connect the PC to
the IP input.
Run the animeo Connect Operating Software and follow the
procedure described in the software guide.
A. „xx" represents the bus system handled by the gate-
way, e.g. io, SDN, ...
Twisted pair
/20 AWG
Required
2
/20 AWG
Required
2
Max. length
1.8 m
100 m
300 m
300 m

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

1860312

Table des Matières