SPLIT-TYPE AIR CONDITIONERS
INSTALLATION MANUAL
1. BEFORE INSTALLATION
1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
• Be sure to read these safety precautions and instructions.
• Be sure to observe the warnings and cautions specified here.
• After reading this manual, be sure to store it with the OPERATING INSTRUCTIONS for future reference.
• Please report to your supply authority or obtain their consent before connecting this equipment to the power supply system.
Do not install the unit by yourself (user).
Improper or incomplete installation could cause fire, electric shock, injury due to the
unit falling, or water leakage. Consult a qualified installer or the dealer from whom
you purchased the unit.
Follow the instructions detailed in the installation manual.
Incomplete installation could cause fire or electric shock, injury due to the unit falling,
or leakage of water.
When installing the unit, use appropriate protective equipment and tools for
safety.
Failure to do so could cause injury.
Install the unit securely in a place that can bear the weight of the unit.
If the installation location cannot bear the weight of the unit, the unit could fall causing
injury.
Perform electrical work according to the installation manual and be sure to use
an exclusive circuit. Do not connect other electrical appliances to the circuit.
If the capacity of the power circuit is insufficient or there is incomplete electrical work,
it could result in a fire or an electric shock.
Ground the unit correctly.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone
ground. Defective grounding could cause electric shock.
Do not damage the wires.
Damaged wires could cause fire.
Be sure to shut off the main power when setting up the indoor P.C. board or
wiring.
Failure to do so could cause electric shock.
Use the specified wires to securely connect the indoor and outdoor units. At-
tach the wires firmly to avoid applying stress to the terminal block.
Improper connection could cause fire.
Do not install the unit in a place where flammable gas may leak.
If gas leaks and accumulates around the unit, it could cause an explosion.
Do not use intermediate connection of the power cord or the extension cord.
Do not connect many devices to one AC outlet.
It could cause a fire or an electric shock.
Use the parts provided or specified parts for the installation work.
The use of defective parts could cause an injury or leakage of water due to a fire, an
electric shock, the unit falling, etc.
When plugging the power supply plug into the outlet, make sure that there is
no dust, blockage, or loose parts both in the outlet and on the plug. Verify that
the power supply plug is completely in the outlet.
If there is dust, blockage, or loose parts on the power supply plug or the outlet, it could
cause electric shock or fire. If loose parts are found on the power supply plug, replace it.
Depending on the installation area, install a Ground Fault Interrupt (GFI) circuit
breaker.
If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric shock
could occur.
Perform the drainage/piping work securely according to the installation
manual.
If there is defect in the drainage/piping work, water could drip from the unit, and
damage household items.
JG79A344H07
MSZ-FE18NA
MSZ-GE24NA
MSY-GE24NA
When installing multi units, refer to the instal-
lation manual of the multi unit for outdoor unit
installation.
WARNING
CAUTION
Required Tools for Installation
Phillips screwdriver
Level
Scale
Utility knife or scissors
3 in. (75 mm) hole saw
Torque wrench
Wrench (or spanner)
(Could lead to death or serious injury.)
Securely attach the electrical cover to the indoor unit and the service panel to
the outdoor unit.
If the electrical cover of the indoor unit and/or the service panel of the outdoor unit are
not attached securely, dust, water, etc. could collect in the unit and could cause a fire or
an electric shock.
When installing, relocating, or servicing the unit, make sure that no substance
other than the specified refrigerant (R410A) enters the refrigerant circuit.
Any presence of foreign substance such as air can cause abnormal pressure rise and
may result in explosion or injury. The use of any refrigerant other than that specified
for the system will cause mechanical failure, system malfunction, or unit breakdown. In
the worst case, this could lead to a serious impediment to securing product safety.
Do not discharge the refrigerant into the atmosphere. Check that the refrigerant gas
does not leak after installation has been completed. If refrigerant leaks during
installation, ventilate the room.
If refrigerant comes in contact with a fire, harmful gas could be generated.
If refrigerant gas leaks indoors, and comes into contact with the flame of a fan heater,
space heater, stove, etc., harmful gases will be generated.
Use appropriate tools and piping materials for installation.
The pressure of R410A is 1.6 times higher than R22. Not using the appropriate tools
and materials, or improper installation could cause the pipes to burst causing an
injury.
When pumping down the refrigerant, stop the compressor before disconnecting
the refrigerant pipes.
If the refrigerant pipes are disconnected while the compressor is running and the
stop valve is open, air could be drawn in and the pressure in the refrigeration cycle
could become abnormally high, causing the pipes to burst.
When installing the unit, securely connect the refrigerant pipes before starting
the compressor.
If the compressor is started before the refrigerant pipes are connected and the stop
valve is open, air could be drawn in and the pressure in the refrigeration cycle could
become abnormally high, causing the pipes to burst.
Fasten a flare nut with a torque wrench as specified in this manual.
If fastened too tight, a flare nut could break and cause refrigerant leakage.
Install the unit according to national wiring regulations.
(Could lead to serious injury when operated incorrectly.)
Do not touch the air inlet or the aluminum fins of the outdoor unit.
This could cause injury.
Do not install the outdoor unit where small animals may live.
If small animals enter the unit and damage its electrical parts, it could cause a mal-
function, smoke emission, or fire. Keep the area around the unit clean.
5/32 in. (4 mm) hexagonal wrench
Flare tool for R410A
Gauge manifold for R410A
Vacuum pump for R410A
Charge hose for R410A
Pipe cutter with reamer

Publicité

Table des Matières
loading

Sommaire des Matières pour Mitsubishi Electric MSZ-FE18NA

  • Page 1 Required Tools for Installation JG79A344H07 MSZ-FE18NA Phillips screwdriver 5/32 in. (4 mm) hexagonal wrench MSZ-GE24NA Level Flare tool for R410A MSY-GE24NA Scale Gauge manifold for R410A Utility knife or scissors Vacuum pump for R410A When installing multi units, refer to the instal- 3 in.
  • Page 2: Selecting The Installation Location

    1-3. SPECIFICATIONS Electrical specifications 1-3-1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION MSZ-FE18NA MODEL MSY-GE24NA • Power should be taken from an exclusive branched circuit. MSZ-GE24NA • Wiring work should be based on applicable technical standards.
  • Page 3: Installation Diagram

    1-4. INSTALLATION DIAGRAM Wall hole cover (D) Use the wall hole sleeve Indoor unit (C) to prevent indoor/out- Seal the wall hole gap with putty (H). ACCESSORIES door connecting wire (A) Check the following parts before installation. f r o m c o n t a c t i n g m e t a l Wall hole Attach the pipe to <Indoor unit>...
  • Page 4: Indoor Unit Installation

    2. INDOOR UNIT INSTALLATION 2-1. ATTACHING THE INSTALLATION PLATE Ceiling 2 1/8 in. (55 mm) or more 4 5/8 in. (118 mm) or more for left • Find a stud in the wall to attach installation plate (1) horizontally by tightening the fixing and left back piping (using spacer) screws (2) firmly.
  • Page 5: Drain Piping

    2-4. PIPE FORMING AND DRAIN PIPING 2-4-1. PIPE FORMING • Place the drain hose below the refrigerant piping. • Make sure that the drain hose is not crowded or bent. Gas pipe Liquid pipe • Do not pull the hose when applying the tape. •...
  • Page 6: Outdoor Unit Installation

    3. OUTDOOR UNIT INSTALLATION 3-1. CONNECTING WIRES FOR OUTDOOR UNIT 1) Remove the service panel. 2) Remove the conduit cover. 3) Attach the conduit connector to conduit plate with lock nut then secure it against unit with screws. 5/8 in. 4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (15 mm) 1-3/8 in.
  • Page 7: Purging Procedures, Leak Test, And Test Run

    3-3. PIPE CONNECTION • Fasten flare nut with a torque wrench as specified in the table above. • When fastened too tight, flare nut may eventually break and cause refrigerant leakage. • Be sure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
  • Page 8: Relocation And Maintenance

    5. RELOCATION AND MAINTENANCE 5-1. REMOVING AND INSTALLING THE PANEL ASSEMBLY Removal procedure 1) Remove the three screws that attach the panel assembly. 2) Remove the panel assembly. Be sure to remove its bottom end first. Installation procedure 1) Install the panel assembly following the removal procedure in reverse. 2) Be sure to press the positions as indicated by the arrows in order to attach the assem- bly completely to the unit.
  • Page 9: Avant L'installation

    Outils nécessaires à l’installation JG79A344H08 MSZ-FE18NA Tournevis Phillips Clé hexagonale de 5/32 in. (4 mm) MSZ-GE24NA Niveau Outil d’évasement pour le modèle R410A MSY-GE24NA Règle graduée Collecteur à jauge pour le modèle R410A Couteau tout usage ou paire de ciseaux Pompe à...
  • Page 10: Choix De L'emplacement D'installation

    à partir de cet emplacement (un ou deux phtalate, le formaldéhyde etc., qui peuvent provoquer un craquage chimique. 1-3. FICHE TECHNIQUE Spécifications électriques 1-3-1. BRANCHEMENT DU CORDON D’ALIMENTATION ET DU CABLE DE MSZ-FE18NA MODELE MSY-GE24NA CONNEXION DE L’UNITE INTERNE/EXTERNE MSZ-GE24NA • L’alimentation doit provenir d’un circuit unique.
  • Page 11: Schema D'installation

    1-4. SCHEMA D’INSTALLATION Cache d’ouverture murale (D) U t i l i s e z l e m a n c h o n Unité d’ouverture murale (C) Bouchez l’ouverture interne pour éviter tout contact en- murale avec du mastic (H). ACCESSOIRES tre le câble de connexion Vérifiez les pièces suivantes avant l’installation.
  • Page 12: Installation De L'unite Interne

    2. INSTALLATION DE L’UNITE INTERNE 2-1. FIXATION DU GABARIT D’INSTALLATION 2-1/8 in. (55 mm) minimum Plafond 4-5/8 in. (118 mm) minimum pour la • Repérez un goujon dans le mur pour fixer le gabarit d’installation (1) horizontalement en tuyauterie gauche ou arrière gauche serrant fermement les vis de fixation (2).
  • Page 13: Mise En Forme De Tuyau Et Tuyau De Vidange

    2-4. MISE EN FORME DE TUYAU ET TUYAU DE VIDANGE Tuyau de liquide Tuyau de gaz 2-4-1. MISE EN FORME DE TUYAU • Placez le tuyau de vidange sous la conduite de réfrigérant. • Assurez-vous que le tuyau de vidange n’est ni encombré ni plié. •...
  • Page 14: Installation De L'unite Externe

    3. INSTALLATION DE L’UNITE EXTERNE 3-1. RACCORDEMENT DES CABLES DE L’UNITE EXTERNE 1) Retirez le panneau de service. 2) Déposez le cache de conduit. 3) Attachez le connecteur de la canalisation électrique à la plaque à l’aide d’un contre-écrou et fixez la plaque sur l’unité avec des vis. 5/8 in.
  • Page 15 3-3. RACCORDEMENT DES TUYAUX • Serrez l’écrou évasé avec une clé dynamométrique comme spécifié dans le tableau ci-dessus. • S’il est trop serré, il risque de se rompre et de provoquer une fuite de réfrigérant. • Assurez-vous que la tuyauterie est enveloppée d’isolant. Un contact direct avec la tuyauterie nue peut entraîner des brûlures ou des engelures.
  • Page 16: Deplacement Et Entretien

    5. DEPLACEMENT ET ENTRETIEN 5-1. DEPOSE ET INSTALLATION DU PANNEAU Dépose 1) Retirez les trois vis de fixation du panneau. 2) Déposez le panneau. Retirez d’abord l’extrémité inférieure. Pose 1) Remontez le panneau en suivant la procédure de dépose en sens inverse. 2) Veillez à...