Electrical installation
Power supply
Max. rated power
Circuit breaker
RCCB
Protection type
Protection class
Position of electrical / water connection
180
IG 1/2"
90
90
Pre-Installation
> Lay a permanent power supply line:
Please observe the position of the electrical
connection
Leave at least 800 mm of feed cable exposed
> Install circuit breaker
Connect a separate upstream circuit breaker
Connect an upstream residual current device (RCD)
separating all poles
> Appliances have to be correctly earthed.
24
Connecting the cable (Diagram 24)
> Please observe the L, N and PE conductors.
26
Installing junction box (Diagram 26)
> Fix the junction box in the Wall-mounted WC in
the designated place.
220 – 240 V ~ 50/60 Hz
1.65 kW
I
= 16 A
N
I
= 30 mA
N
IP X4
1
Water installation
Cold water
DN 15(1/2")
Water pressure
0.07 – 0.75 MPa
(0.7 – 7.5 bar)
Water hardness
max. 2,4 mmol/l
NOTE!
> Install a water water softener with water
hardness ≥ 2.4 mmol/l
(≥ 14° dH and/or 24° fH).
Pre-Installation
> Install the water connection and water outlet in the
specified areas.
DANGER!
Health risk and potential product damage.
> Supply the Shower WC with cold drinking water from
the main water system.
> Do not connect any waste water, grey water, industrial
water, sea water or other untreated or semi-treated
water.
11
Connecting the water (Diagram 11)
NOTE! Avoiding any malfunctions!
> Only use the water supply hoses provided.
SensoWash_MAL_WWC_53978/15.01.8