poolstar Poolex Platinium Mini Manuel D'installation Et D'utilisation page 73

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1
Poolex Platinium Mini 7
DC FAN CAPACITOR
Reactive
resistance
CN-RAT1
U
V
W
RED
WHI
BLU
CN-RAT2
V
W
U
MC
Compressor
12V GND A B
CN6
Wire controller
10.2
Error E20 complement
Code
Anomalies
1
IPM excessive current
2
Compressor failure
4
Reserved
8
Compressor lack of phase
16
DC bus voltage too low
32
DC bus voltage too high
64
Temp of radiating fin too high
128
Temp of radiating fin failure
257
Connection failure
258
AC input lack of phase
260
AC input voltage to high
AC input voltage too low
264
272
High pressure failure
IPM temp too high
288
320
Compressor current too high
384
Reserved
10. Appendices
MF
EGND
CN4
DC FAN
Water flow switch
Low Pressure Switch
RED
WHI
YLW(or)BLK
BRN
Electronic
expansion valve
IN3
IN2
IN1
T6
T7
T5
T4
T3
T8
Reserved
Outlet water temp
Ambient temp
5K
5K
Causes possibles
IPM module failure
Compressor failure
--
The wire for the compressor break/bad connection
Input voltage too low/PFC module failure
Input voltage too high/PFC module failure
Fan motor failure/Air duct blockage
Radiating fin temp sensor short circuit or open circuit failure
Inverter module doesn't receive the command of PCB
Input lack of phase
Input three-phase unbalance
Input voltage too low
Compressor pressure too high (reserved)
Fan motor failure/Air duct blockage
The current of the compressor wiring too high/ Driver and
compressor do not match
--
AC-N
N
L
AC-L
RY1
OUT1
RY2
OUT2
RY3
OUT3
BLU
RY4
OUT4
RY5
OUT5
LED
RY6
CN5
OUT6
CN3
RY7
OUT7
T2
T1
RY8
OUT8
Exhaust temp
Inlet water temp
Condenser temp
Replace the inverter module
Replace the compressor
--
Check the wire connection of the compressor
Check input voltage/replace module
Replace the inverter module
Check fan motor/air duct
Replace the inverter module
Check the connection between the module and PCB
Check the wire connection
Check input the 3-phase voltage
Check input voltage
--
Check fan motor/air duct
Replace the inverter module
--
37
RED
BRN
4-way valve
BLU
BRN
BLK
BLK
RED
L
N
P1 P2
Y/G
Power: AC
To pump
220-240V/50Hz
220-240V~/50Hz
Actions

Publicité

Table des Matières
loading

Table des Matières