ELLIPSE
3.1.
CLEAN AIR ACT RESTRICTOR KIT – DEFRA – (ONLY FOR UK
SMOKE CONTROL AREAS)
To comply with the requirements of the United Kingdom Clean Air Act, for use
of appliances in smoke control areas, a permanent stop (SF07224) must be
fitted to prevent closure of the secondary air control beyond 40%. This should
be fitted as shown in Picture 2.
4.
FIRE SAFETY MEASURES
While installing the appliance, it is necessary to respect the following safety
measures:
a) In order to ensure sufficient thermal insulation, respect the minimum
safety distance from objects or furnishing components flammable and sensitive to heat (furniture, wood
sheathings, fabrics. etc.) and from materials with flammable structure (see Picture 3 A1-A2). All the
minimum safety distances are shown on the product data plate and lower values must not be
used.
b) In front of the hearth, in its radiation area and its rotation space (+- 45° ) there must not be any
flammable object or construction material sensitive to the heat at least within 100 cm; This distance
can be reduced to 40 cm if you will install in front of the element to protect a retro ventilated and heat
resistant protection.
c) If the product is installed on a non totally refractory floor, one must foresee a fireproof background. The
floors made of inflammable material, such as moquette, parquet or cork etc., must be replaced by
a layer of no-inflammable material, for instance ceramic, stone, glass or steel etc. (size according to
regional filing). The platform must stick out 50 cm in front and 20cm sideways, considering also the
rotation field of the stove. (see Picture 3 B1-B2).
d) no flammable components (e.g. wall units) must be present above the product.