9.

ELECTRICAL CONNECTIONS

B E F O R E
S T A R T I N G
OPERATION, MAKE SURE THAT THE
MAIN POWER SUPPLY LINE HAS
BEEN ISOLATED
P E R F O R M T H E C O N N E C T I O N S
WITH CABLES FEATURING CABLES
FEATURING A SUITABLE CROSS-
SECTION
The electric connections to the
control board must be made by
specialised staff according to
the diagram supplied.
Make sure that the voltage and
the frequency stated on the
plate correspond with those of
the electric connection line.
The use of adapters, multiple
s o c ke t s a n d /o r ex t e n s i o n s
is not allowed to power the
dehumidifier.
It is the installer's responsibility
to assemble the unit as near as
possible to the power supply
isolator and the necessary to
protect the electric parts.
Connect the unit to an efficient
earth socket, using the relevant
screw inserted in the unit itself.
Use the cable gland (external
for horizontal versions, internal
for the recessed version) near
the panel to turn it on.
CONNECTION
TYPE I/O
S01 - GND
Analog input
S02 - GND
Analog input
ID1 - GND
Digital input
ID2 - GND
Digital input
ID3 - GND
Digital input
ID4 - GND
Digital input
R01 - GND
Digital output
R02 - GND
Digital output
R03 - GND
Digital output
R07 - GND
Digital output
(*) the installer is responsible for any external circuit
(**) The contact in question is normally open and closes in the event of an alarm on the unit: can be connected, for example, as a consensus for powering on
a LED alarm signal.
A N Y
FORCED AIR HEATER MODE ON/OFF
ON/OFF MODALITA' TERMOVENTILANTE
POTENTIAL FREE CONTACT
VENTILATORE
MEANING I/O
Water input temperature
Inlet air temperature
High pressure switch
Low pressure switch
Humidistat consent
Forced air heater mode On/Off
Compressor consent
Alarm circuit (230 V) (*)
Fan consent
Set-up (potential free contact)(**)
GND
WATER PROBE
SONDA ACQUA
[S01]
GND
AIR PROBE
SONDA ARIA
[S02]
S02
GND
HUMIDISTAT
[ID3]
UMIDOSTATO
TIMER
GND
[ID4]
RES
GND
LOW PRESSURE
BASSA PRESSIONE
[ID2]
BP
GND
HIGH PRESSURE
ALTA PRESSIONE
[ID1]
HP
GND
[R07]
CONTATTO PULITO
INT
PER ALLARME
FOR ALARM
ALL (230V)
[R02]
Common
Comune/Common
White
FAN
Bianco
min
min
Red
Rosso
[R03]
average
med
Blue
Blu
max
max
Black
Nero
COMPRESSOR
COMPRESSORE
[R01]
230 V / 50 Hz/ 1 ph
HP pressure switch status
BP pressure switch status
Dehumidifier status
Thermoventilating state
Compressor status
Circuit alarm status
Fan status
Circuit alarm status
EN
S01
250mA
230 V
P
STATE I/O
Probe reading S01
Probe reading S02
0 = Closed
1 = Open (Warning)
0 = Closed
1 = Open (Warning)
0 = Off
1 = On
0 = Off
1 = On
0 = Off
1 = On
0 = Absent
1 = current
0 = Off
1 = On
0 = Absent
1 = current