6- Special case:
INHIBITING the charging alternator
alarm
6.1 Mitsubishi & some Lombardini
(KDI) engines
Connect the additional wiring
harness to the C3 connector,
removing the shunt from it (Fig.9)
Cable the other end (wire 61A) to
termination box B01 terminal 2
(Fig.10)
6.2 Lombardini engine (KDW1003
and 1404)
Clip the terminal with the resistor
onto the upper rail on the control
panel base plate
(Fig.11)
Connect the additional wiring
harness to the C3 connector,
removing the shunt from it
Cable the other end (wire 61A) to
termination box B01 terminal 2
Cable the other end (wire 80) to
termination box K4 terminal 3 (wire
80)
In all cases, refer to the diagram
If it is non-operational, contact the SDMO after-sales service