MOUNTING
After enrolling and before mounting permanently, conduct Go/No Go tests
(see the Control Panel's instructions) to verify adequate signal strength.
Adjust the device location and orientation as necessary.
TESTING
After enrolling, verify adequate signal strength by conducting a sensor test (see the controller's
instructions) with the device in its intended mounting location. Adjust the device location and orientation
as necessary.
NOTES:
Notify the proper authorities that the smoke detector is undergoing testing.
All smoke detectors programmed to operate in One-Go-All-Go mode will sound on alarm.
To silence the detector:
Press the Test Button or disarm the system at
the controller. The detector sounds again after
10 minutes if the alarm condition continues.
When programmed in one-go-all-go mode, the
detector can only be silenced from the
controller.
BATTERY REPLACEMENT
NOTE: Do not mix old and new batteries, battery types or
manufacturers. Constant exposure to high or low temperature or
high humidity may reduce battery life.
Battery Caution: Risk of fire, explosion and burns. Do not recharge,
disassemble, heat above 212 ° F (100 ° C) or incinerate. Dispose of used
batteries properly. Keep away from children.
NOTE: Batteries available at your local retailer or distribution center.
CLEANING
NOTE: To prevent unwanted alarms and possible dispatch
of the fire department, disable the zone or system undergoing
maintenance. Notify the proper authorities that the smoke
detector is undergoing maintenance and the system will
temporarily be out of service.
NOTE: Smoke detectors are not to be used with detector guards unless the combination is
evaluated and found suitable for that purpose.
Product must be tested at least once each year
REFER TO THE INSTALLATION INSTRUCTIONS FOR THE CONTROL WITH WHICH THIS DEVICE IS
USED, FOR DETAILS REGARDING LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Application Guides (www.resideo.com)
See the Limitations of Fire Alarm Systems Insert (P/N 800-15144 5/13).
Specifications / Spécifications
RF Frequency / Fréquence RF: 2.4GHz
Battery / Pile: 2 x 3V, Lithium; Panasonic CR123A, Resideo 466
Tamper / Sabotage : Base / Base
Operating Temperature / Température de fonctionnement: 40° to 100° F / 4.4° to 37.7° C
Relative Humidity / Humidité relative: 95% max. (Agency Compliance – 93% max.), non-condensing / (Agence de
conformité – 93% max.), sans condensation
Maximum Spacing / Espacement maximal : 50ft x 50ft / 15 m x 15 m [refer to National Fire Alarm Code Standard
NFPA 72 for application requirements] / [Pour connaître les exigences à remplir, reportez-vous à la NFPA 72.]
Dimensions / Dimensions : 4.5 in. Diameter x 1.7 in. Thick / 11.9 cm Diameter x 4.5 cm Thick / Diamètre de
11,9 cm x épaisseur de 4,5 cm/Diamètre de 4,5 po x épaisseur de 1,7 po
FEDERAL COMMUNICATIONS COMMISSION & INDUSTRY CANADA STATEMENTS
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's
authority to operate the equipment.
FCC / IC STATEMENT This device complies with Part 15 of the FCC Rules, and Industry Canada's license-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la partie 15 des règles de la FCC et exempt de licence RSS d'Industrie Canada. Son fonctionnement est soumis aux conditions suivantes: (1) Cet appareil ne doit pas causer
d'interférences nuisibles. (2) Cet appareil doit accepter toute interférence reçue y compris les interférences causant une réception indésirable.
RF EXPOSURE WARNING – The antenna(s) used for this device must be installed to provide a separation distance of at least 7.8 inches (20 cm) from all persons and must not be co-located or operating in
conjunction with any other antenna or transmitter except in accordance with FCC multi-transmitter product procedures.
MISE EN GARDE EXPOSITION AUX FREQUENCES RADIO: L'antenne (s) utilisée pour cet émetteur doit être installée à une distance de séparation d'au moins 7,8 pouces (20 cm) de toutes les personnes.
Responsible Party / Issuer of Supplier's Declaration of Conformity: Ademco Inc., a subsidiary of Resideo Technologies,
Inc., 2 Corporate Center Drive., Melville, NY 11747, Ph: 516-577-2000
The product should not be disposed of with other household waste. Check for the nearest authorized collection centers
or authorized recyclers. The correct disposal of end-of-life equipment will help prevent potential negative consequences
for the environment and human health.
Any attempt to reverse-engineer this device by decoding proprietary protocols, de-compiling firmware, or any similar
actions is strictly prohibited.
800-25552C 5/19 Rev C Part 1
This product is manufactured by Resideo Technologies, Inc. and its affiliates.
MONTAGE
Après avoir enrôlé l'unité et avant de la mettre en place de façon
permanente, effectuez des tests Tout ou rien (voir les instructions du
panneau de commande) pour vérifier que la puissance du signal est
adéquate. Au besoin, modifiez l'emplacement ou l'orientation du dispositif.
MISE À L'ESSAI
Après l'enregistrement, confirmer que la puissance du signal est adéquate en effectuant des tests du
capteur (consulter les instructions du contrôleur) alors que le périphérique est installé à l'endroit
souhaité. Au besoin, ajuster l'emplacement du périphérique et son orientation
NOTES:
Avisez les personnes compétentes qu'un détecteur de fumée est en phase de test.
Tous les détecteurs de fumée programmés pour fonctionner en mode « Une seule fois pour tout »
retentiront.
REMPLACEMENT DE LA PILE
REMARQUE : Ne pas mélange les piles usagées et les piles neuves,
les piles de différents types ou de différentes marques. Une
constante exposition à des températures basses ou élevées, ou à un
tau d'humidité élevé, peut réduire la durée de vie de la
pile.Précautions concernant les piles : Risques d'incendie, d'explosion
et de brûlure. Ne pas recharger, démonter, chauffer à plus de 100 ° C
(212 ° F) ou incinérer. Jeterles piles usagées de manière appropriée.
Tenir hors de la portée des enfants.
REMARQUE: Vous pouvez vous procurer les piles chez votre
détaillant local ou au centre de distribution.
NETTOYAGE
REMARQUE : Pour éviter toute alarme indésirable et un
éventuelappel au service des pompiers, désactiver la zone
ou le système faisant l'objet d'ue maintenance. Informer les
autorités compétentes que le système de détection de fumée
est en cours de maintenance sera par conséquent
temporairement hors service.
REMARQUE: Les détecteurs de fumée ne sont pas conçus pour être utilisés avec des
protecteurs de détecteur à moins que cette utilisation ait été évaluée et trouvée acceptable
Le fonctionnement du produit doit être vérifié au moins une fois par année
POUR LES LIMITES DU SYSTÈME D'ALARME AU COMPLET, REPORTEZ-VOUS AU GUIDE
D'INSTALLATION DU PANNEAU DE COMMANDE.
Guides d'application (www.resideo.com)
Consulter l'encart Restrictions des systèmes d'alarme incendie (réf. 800-15144 5/13).
Support / Soutien
www.resideo.com
Approval Listings / Approbations
Homologations
FCC / IC
ETL Listed to UL268 & CAN/ULC S529
State of California requirement – free of substances that may cause cancer. Prop
65 US.
Exigence de l'État de la Californie – ne conteniraucune substance
cancérigène. Proposition 65 des États-Unis.
Partie responsable / Émetteur de la déclaration de conformité du fournisseur : Ademco Inc., une filiale de Resideo
Technologies, Inc., 2 Corporate Center Drive., Melville, NY 11747, Tél. 516 577-2000
Ce produit ne doit pas être jeté avec les ordures ménagères. Recherchez les centres de collecte ou de recyclage
autorisés les plus près de chez vous. L'élimination adéquate d'équipement en fin de vie permet d'éviter les
conséquences néfastes sur l'environnement et sur la santé humaine.
Toute tentative d'ingénierie inverse de cet appareil,en décodant les protocoles propriétaires, en décompilant le logiciel
microprogramme ou en effectuant toute mesure similaire est strictement interdite.
Pour faire taire le détecteur :
Appuyer sur le bouton Test ou désarmer le
système à partir de l'unité de commande
Le détecteur sonnera de nouveau après
10 minutes si la situation d'alarme
persiste. Lorque le détecteur est
programmé en mode (« one-go-all-go »),
le détecteur ne peut êtrearrêté qu-à partir
de l'unité de commande.
U.S. warranty / U.S. garantie
www.security.honeywellhome.com/warranty
2 Corporate Center Drive, Suite 100
P.O. Box 9040, Melville, NY 11747
© 2020 Resideo Technologies, Inc.