Wiring; Configuration - AKO 55323 Manuel D'utilisateur

Masquer les pouces Voir aussi pour 55323:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Wiring

The wiring between the detector/button and the station should NEVER be installed in a conduit together with power,
control or feeder cables.
Always disconnect the power supply to do the wiring.
The power supply circuit should be equipped with a switch for its disconnection of at least 2 A, 230 V,
situated near the appliance. The power supply cable will be H05VV-F or NYM-1x16/3. The section to be
used will depend on current local regulations, but should never be less than 1.5 mm .
Cables for wiring the relay contact should have an adequate section depending on the unit to be connected.
The 120 / 230 V~ wiring must be kept clear of any other external element.
Make sure you have connected the batteries before starting-up the unit.
Pursuant to RD 138/2011 IF12 (SP) and standard EN-378-1 (EU), the Alarm's power supply must come from a
different circuit than the one used for the cooling and ventilation system.
AKO-5512x
Alarm 1 (With battery)
Input
RS485
AKO-55123 / 55323:
15V
Out

5.- Configuration

Self-diagnosis function
The equipment includes a self-diagnosis system that informs the user in the event of a malfunction in the detector
or push-button or if there are errors in the wiring.
If a malfunction is detected, the alarm emits 3 short beeps every 2 minutes and the corresponding input indicator
flashes red.
ALARM
Alarm relay
Vac
NO
C
NC
230 V~ ± 10%
50 - 60 Hz
AKO-55120: 120 V~ + 8% - 12 %
50 - 60 Hz
AKO-55326
14
AKO-55323
ALARM
Alarm 2 (Only AKO-55323B, without battery)
Input
Alarm relay
RS485
NO
C
15V
Out
AKO-55326
5532H301 Ed.02
2
Vac
NC
230 V~ ± 10%
50 - 60 Hz

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

5512355120

Table des Matières