INTRODUCTION

Network module "Ping2" is intended for connection of KOMFOVENT air handling units to the computer network
(Ethernet) or another network ("RS-485"). If "Ping2" module is not added by factory, it can be installed on each
air handling unit (AHU) with C3 or C4 controller. For this case user need to have installation kit:
1. Network module ("Ping2").
2. Additional connection cable (5 m.).
3. Installation Manual.

1. NETWORK MODULE INSTALLATION

1. Network module can be installed provided place under given following conditions:
● ambient temperature range 0 °C ... 40 °C;
● relative humidity limits 20 % ... 80 %;
● protection must be ensured from accidentally vertically falling water drops (IP X2).
Cable length between AHU and "Ping2" module can't exceed more
then 50 m with type 4 × 0.22 mm
4 × 0.35 mm
10
.
2
UAB KOMFOVENT we reserve the right to make changes without prior notice
or not more 100 m with type
2
PING2-16-10