INSTALLATION MANUAL
ARD12T
Rectifi ed and fi ltered PSU with Time-delay Relay and low power regulated output
PRODUCT PRESENTATION
Regulated PSU.
Primary and secondary inputs
protected by automatic fuses.
Input voltage: 230V ± 10%, 50/60 Hz.
Power consumption: 0.15A.
Relays features:
- Time-delay relays, dry contacts NO/NF (8A/250V).
- Time delay adjustable from 0.5 to 3.5 seconds.
Outputs:
- Main: 12V dc rectifi ed and fi ltered
and non-regulated for electromagnet
or strike input voltage.
- Secondary: 12Vdc regulated*.
Maximum load current:
- Main output only = 1,5A,
- Secondary output only = 1A,
- Divided on the 2 outputs = 1,5A.
Green LED indicates presence of output voltage.
Wall fi xing (screw and plastic anchor included)*
Inputs and outputs protected by resettable fuses.
(After an overload or short-circuit, disconnect
the network for 1 minute to reset the fuse.)
SORTIES BORNIERS
4
5
6
7
8
9
10
N
L
COMPLIANT WITH EUROPEAN STANDARDS
EN 55022
EN 61000-4-2
EN 61000-3-2
EN 61000-4-3
EN 61000-3-3
EN 61000-4-4
This product must be installed in accordance
with the local safety standards.
cdvi.com
2
cdvigroup.com
TENSION
Relay command (0V)
Normally open (N/O)
Common (C)
Normally closed (N/C)
+12V dc non-regulated
0V
+12V dc regulated
230V ac
230V ac
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
*Wall fi xing
on each side
WEEE & RoHS
IP20
Specifi ed time
adjustement
Mains terminal block
cover in the event
of mounting outside
a standard electrical
equipment box.
* Suitable to low consumption devices.
6% wave rate appears on the regulated output for a 600mA
current divided between the 2 outputs.
CE certifi cation
-25°C to +55°C