LoRaWAN Smart Building MOTION - Guide utilisateur / User guide version V1.0.0
3.3.1.04
Registers that configure digital input alarm(s)
Register
Size
(bytes)
S380
1
FR
EN
S381
2
S382
1
S383
2
Description
Configuration of the button (Digital
Input 1)
Button alarm threshold (Digital
Input 1)
Configuration of the terminal block
(Digital Input 2)
Terminal alarm threshold (Digital
Input 2)
Encoding
Details
Hexadecimal
Default: 0x41
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 1 detection counter becomes great-
er than this threshold, an alarm is triggered
Hexadecimal
Default: 0x0
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 2 detection counter becomes great-
er than this threshold, an alarm is triggered