8.2
Allocation of fuses, phases and slots
Model No.
PDU infeed
DK
7955.X01
230 V/1~/16 A
7955.X10
230 V/1~/16 A
7955.X11
230 V/1~/32 A
7955.X31
400 V/3~/16 A
7955.X32
400 V/3~/16 A
7955.X33
400 V/3~/32 A
7955.X34
400 V/3~/32 A
7955.X35
400 V/3~/16 A
7955.X36
400 V/3~/32 A
Tab 1:
Allocation of fuses – PDU international versions
Model No.
DK
String 1 (F1)
7955.X01
12 x C13
24 x C13 +
7955.X10
4 x C19
12 x C13 +
7955.X11
2 x C19
6 x C13 +
7955.X31
1 x C19
8 x C13 +
7955.X32
2 x C19
7955.X33
8 x C13
6 x C13 +
7955.X34
1 x C19
7955.X35
14 x C13
7955.X36
8 x C13
Tab 2:
Allocation of phases and slots – PDU international versions
Rittal PDU international/PDU UK power distribution unit
Fuse
(type C16 A)
–
–
2 x
–
–
6 x
6 x
–
6 x
Phase 1
String 1 (F2)
String 2 (F1)
–
–
12 x C13 +
2 x C19
6 x C13 +
–
1 x C19
8 x C13 +
–
2 x C19
2 x C19
8 x C13
6 x C13 +
6 x C13 +
1 x C19
1 x C19
–
14 x C13
8 x C13
8 x C13
Total slots
C13
C19
12
24
24
18
24
24
36
42
48
Phase 2
String 2 (F2)
–
–
–
–
–
–
–
–
2 x C19
6 x C13 +
1 x C19
–
8 x C13
Technical specifications
–
4
4
3
6
6
6
–
–
Phase 3
String 3 (F1)
String 3 (F2)
–
–
–
–
–
–
6 x C13 +
–
1 x C19
8 x C13 +
–
2 x C19
8 x C13
2 x C19
6 x C13 +
6 x C13 +
1 x C19
1 x C19
14 x C13
–
8 x C13
8 x C13
EN
27