Setting Jumper positions on Cat. No. NPRPT-006
WARNING: Ensure that only one power supply is providing power to
each segment. Jumpers have been provided to allow you to isolate
power to any part of the network.
Port B-F Jumpers installed on pins:
• 1-2 – Bridge Power between this port and port to right (ex: if jumper
is installed on Ports F 3+4, then power is bridged between Port F &
Port E).
• 2-3 – No function (default configuration).
• 3-4 – Power repeater from power supply on this port.
Port A jumpers installed on pins:
• 1-2 – No function.
• 2-3 – No function (default configuration).
• 3-4 – Power repeater from power supply on this port.
JUMPER SETTINGS NPRPT-006
NPRPT-006
Port F
Jumper
4 3 2 1
4 3 2 1
4 3 2 1
Port F
Port E
Port D
4 3 2 1
4 3 2 1
Port C
Port B
Port A
Termination
Switch
Page 9
Advanced
Configuration
Switch
4 3 2 1
Port A