DIP SW
Description
Charge Current:
4
ON:* 400 mA Charge current
OFF: 200 mA Charge current
Override Battery Discharge Protection:
5
ON: The battery may be totally discharged during continuous
AC failure, thus battery replacement may be required (no deep
discharge protection).
Note: In this position, the repeater will start to operate from a battery
whether it is connected to the mains or not.
OFF:* If an AC power occurs, the repeater automatically disconnects
the battery when its backup battery voltage drops below 3.2 VDC in
order to prevent deep discharge that may damage the battery.
Note: In this position, the repeater will not start to operate from a battery
power supply unless first connected to the mains.
Spare
6
Spare
7
Programmer Mode:
8
ON: Programmer Mode (for factory use)
OFF:* Normal Operation
* Default
3. LED Indication
GREEN
Flashes: Normal operation mode
RED
ON: Battery charging
OFF: Discharging state or Charging problem (a trouble condition
will also exist in the panel and the the Orange LED will flash) or
battery status LED is disabled
BLUE
Flashes (1 sec.): Add / remove device from receiver.
Repeater transmitting
Flashes rapidly: Repeater upgrade
ORANGE
Flashes: Trouble
4