Manual Motor
Controllers
140MP-A3E-A16
140MP-A3E-A25
140MP-A3E-A40
140MP-A3E-A63
140MP-A3E-B10
140MP-A3E-B16
140MP-A3E-B25
140MP-A3E-B40
140MP-A3E-B63
140MP-A3E-C10
140MP-A3E-C12
140MP-A3E-C16 (1)
140MP-A3E-C20
140MP-A3E-C25 (2)
140MP-A3E-C25 (2)
140MP-A3E-C32 (3)
(1) Limited to 15.5 FLA maximum when used in a 365 mm x 235 mm x 140 mm (200 %) or larger enclosure.
Limited to 14.5 FLA maximum when used in 115 mm x 290 mm x 180 mm (150 %) minimum sized enclosure.
(2) Minimum enclosure size is 170 mm x 670 mm x 235 mm (250 %) at full load current.
If end use current is 22.5 FLA or less, may be used in an enclosure as small as 115 mm x 290 mm x 180 mm (150 %).
(3) May be used at 30.8 FLA maximum when used in surrounding air of 40 Deg C maximum.
May be used up to 29 FLA when used in a 115 mm x 290 mm x 180 mm (150 %) minimum size enclosure.
(4) 140MP-A-PEC23 connection modules may be used with 100-C09 thru -C23 up to 24A.
Publication 140MP-IN002B-EN-E - March 2021
Type 1 Coordination SCCR
Contactors
480 Vac
(4)
[A]
30,000
30,000
30,000
30,000
100-C09
30,000
100-C12
100-C16
30,000
100-C23
30,000
18,000
18,000
18,000
100-C12
100-C16
18,000
100-C23
100-C16
18,000
100-C23
100-C23
100-C30
18,000
100-C37
100-C23
18,000
100-C30
18,000
100-C37
100-C30
18,000
100-C37
Installation instruction for Manual motor starter
600 Vac
[A]
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
5,000
–
5,000
5,000
DIR 10004508033 (Version 02)
5/8
Maximum Fuse
or Circuit Breaker
sized per NEC [A]
175
175
175
175
175
175
175
175
175
175
175
175
400
400
400
400