SET DISPLAY SLEEP MODE
Sets the LCD display SLEEP mode
Command:
!SET_SLEEPMODE xxx<CR>
xxx = {30SEC, 60SEC, OFF}
If specified display sleep mode is invalid
Action:
No action will be taken, UPS will request a valid mode setting
Response from UPS:
$INVALID_PARAMETER<CR>
$SLEEP_MODE = xxx<CR>
RESET FACTORY SETTINGS
Resets all of the custom configuration settings
Send to UPS:
!RESET_ALL<CR>
Action:
Sets all state variables to the default values
Response from UPS:
$FACTORY SETTINGS RESTORED<CR>
SEND QUERIES
IDENTIFY
Request that the unit identify itself.
Send Query to UPS:
?ID<CR>
Action:
Model number and firmware revision will be provided.
Response:
$FURMAN<CR>
$F1000-UPS<CR>
$FIRMWARE revision<CR>
OUTLET STATUS
Requests the on/off status of the outlet banks
Send Query to UPS:
?OUTLETSTAT<CR>
status = {ON, OFF}
Action:
On/off status for outlets will be provided.
Response:
$BANK1 = status<CR>
$BANK2 = status<CR>
POWER STATUS
Requests the status of the input voltage. The responses are the same as Power Fault Status Change.
Send Query to UPS:
?POWERSTAT<CR>
Action:
Power status messages will be returned
Response:
Normal operation
$PWR = NORMAL<CR>
Overvoltage
$PWR = OVERVOLTAGE<CR>
Undervoltage
$PWR = UNDERVOLTAGE<CR>
Lost Power
$PWR = LOST POWER<CR>
Test Mode
$PWR = TEST<CR>
13