• Output cables having a modular plug ( similar
to a telephone connector) must never be
connected to a telephone outlet.
• Products with a welded plastic housing or rated
IP 67 are not repairable. For such products the
supply cord cannot be replaced. If the cord is
damaged the appliance should be scrapped.
Please contact your supplier for replacement
part.
• This product contains hazardous voltages and
there are no user replaceable parts inside the
product. Never attempt to remove the cover.
• WARNING: No modification of this equipment
is allowed. Any repair/service should be
carried out by qualified personnel who may get
assistance by contacting the manufacturer or
the manufacturer's agent.
• Products specified to have automatic polarity
protection must be switched off if a battery is
connected with reverse polarity. The protection
will be automatically reset when the polarity
has been corrected.
• In chargers specified to have a replaceable fuse
as polarity protection the fuse must be replaced
if the battery has been connected with reverse
polarity. When replacing the fuse; a fuse of the
same type and rating must be used.
• If the product is specified to comply with the
standard for Medical Electrical Equipment
(standards based on IEC60601-1) it
complies with some of the requirements for
medical electrical equipment and may be
used in medical applications and hospital
environments.
• The product must be kept away from sources
of heat and may not be used in the vicinity
of flammable anesthetic gases or in other
environments with flammable or explosive
atmosphere.
• If the product is specified to comply with the
standard for Medical Electrical Equipment
for Home Healthcare Environment (standard
IEC60601-1-11) it may be used in medical
applications used in a home healthcare
environment.
NOTE: Products relying on safety earth for
protection (Class I) may not be used in home
healthcare environment unless they are
permanently wired to the building installation:
Installation must only be carried out by
qualified service personnel, following the below
instructions:
- The protective earth conductor must be min.
0.75 mm
.
2
- Connect the protective earth conductor to the
external protective earthing system.
- Verify that the protective earth terminal used is
connected to the external protective earthing
system.
- Verify the integrity of the external protective
earthing system.
• This product converts the mains voltage to a
safety extra low voltage.
The output from products applying with 2MOPP
insulation ( model names followed by "P") may
be treated as Applied Part Type B or Type BF
according to standard EN/IEC 60601-1 and
may come in physical contact with a patient.
The housing of the product shall not be allowed
to contact the patient .
• This product must be operated in an
environment within temperature range +5
to +40°C, humidity 15 - 93 % RH and
atmospheric pressure 70 - 106 kPa (700 -
1060 hPa). If the product has recently been
stored or transported at conditions ouside
this range; please wait for 30 minutes before
operating the product.
• Expected service life of this product and
accessories delivered with this product is
three (3) years, if operated as indicated above.
However; the guarantee times indicated in
document "TERMS OF SALES AND DELIVERY
FOR MASCOT AS" apply (available at www.
mascot.com).
• Environmental parameters during transport
and storage between uses: temperature range
4