Icar MCP4 Notice D'utilisation page 17

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

parameters to be programmed, showing their current values.
The correspondence between parameters to be programmed and the measures leds is
shown in the table below:
Led
V
I
Thd%
Thd% +
I harm
Temp.
Over-temperature threshold
Temp. +
I harm
All leds off
V
Voltage transformer ratio
blinking
Current threshold (in % of
I
blinking
Thd% for high current and
Thd%
blinking
Temp.
Temperature offset parameter
blinking
Use the keys +/MAX and -/MIN to change the value of actual parameter and the key
SCROLL to access the next parameters.
Pressing the key RESET/PHASE (for 5 seconds) will force the default value of the
parameter.
To exit the setup mode, wait for 10 seconds without pressing any key: finally the device
will come back to measure mode.
Parameter
Voltage threshold
Primary current
of current transformer
Thd% threshold
for high currents
Trip time Thd alarm
Temperature threshold
for cooling device
(delta value respect to
temperature threshold)
Alarm reset type
(.../100V)
nominal value) between
Thd% for low current
Thd% threshold
for low currents
Programmable Values
from 85 to 540V
from 5 to 10kA
from 5% to 250%
from 5 to 900sec
from 25°C to 50°C
from 0°C to 30°C
AU1 = Automatic reset (mod. 1)
AU2 = Automatic reset (mod. 2)
MAn = Manual reset with
RESET/PHASE key
{1; 2.2; 3.8; 4.4; 5; 6; 8; 10}
from 0% to 100%
from 5% to 250%
from -15°C to 15°C
16
Default
440V
600A
35%
120sec
35°C
25°C
AU1
1
10%
70%
0°C

Publicité

Table des Matières
loading

Table des Matières