USER PARAMETER CONFIGURATION - PROBE READING
Push the up and down buttons simultaneously and hold down for more than 3
seconds.
The label [Loc] is visualised.
Utilise the up and down buttons to scroll the sensor probe readings and the user
parameters.
Press the enter key to confirm your selection and enter the mode for reading probes
or changing parameters.
The current value blinks on the display.
Use the keys
Press the enter key to exit or confirm the selection of the parameter new value; the
setting stops blinking.
Information accessible to qualified staff only.
On starting the appliance, a "LAMPTEST" phase will start.
If you press the enter key 3 times consecutively during this phase, all default
parameters will be reset.
The display shows [rLd] indicating the reset of the values pre-set by the
manufacturer.
ATTENTION: the default values in memory refer to the configurations (tn, bts, btv, PrA) exclusively.
UNIT WITH BROKEN SENSOR PROBES DURING CONSERVATION
Room probe error
If the room probe is broken or the relevant connection interrupted, the display shows the label [E0].
The appliance keeps operating in storing according to the values given to parameters C5 and C6.
The inner fan keeps operating according to the value given to "F3"
Evaporator fan error (only on -22°C / +5°C units)
If the room probe is broken or the relevant connection interrupted, the display shows the label [E1].
The inner fan operates according to the value given to parameter "F3".
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
Humidity sensor Error (only on +14°C/+16°C units)
In the event that the humidity sensor is broken or its connection is interrupted on the display the label [E8], is
visualised; the humidity control device is automatically deactivated.
Condenser probe error
If the condenser probe is broken or the relevant connection interrupted, the display shows the label [E2].
The condenser fan keeps operating according to the value given to parameter "F8".
If the three probes are broken or disconnected, E0, E1, and E2 alternate on the display.
to select the new value, applicable to parameters only.
DEFAULT PARAMETER RECOVERY
ALARMS
23