7.1 Floor-mounted unit
 Set up heater fan in a vertical position.
Ensure that unit is level and stable.
7.2 Wall assembly
Risk of injury and burns if
the unit is incorrectly wall
mounted.
DANGER
 Only mount the unit on a wall
with adequate load-bearing
capacity and characteristics.
Note the weight of the unit.
 The appropriate mounting
material must be supplied by
the customer.
Prescribed minimum distances
 Use the wall bracket [3] supplied to mount
the unit.
 Make sure there is a flat surface to mount
the wall bracket on.
 Attach the wall bracket to the wall with
suitable fixing material ("S1", not included).
 Suspend the unit from the centre of the wall
bracket as shown in the diagram below
using the tubular stand.
 Make sure the unit is level. The control
panel must be easily accessible.
 Screw locking bolt "S2" fully into the wall
bracket to ensure that the unit is securely
bolted to the wall.

7.3 Electrical connection

● The connecting cable for 400 V units is to
be supplied by the customer.
● Fuse protection with 3-way circuit-breaker
is required for 400 V units:
– PHD 5 and PHD 9 with 16 A for each
phase
– PHD 15 and PHD 20 with 32 A for each
phase
 For the sake of security operate the unit
with a residual current device RCD (max.
30 mA).
.