4.6

Settings

The properties of the inverter can be set using the DIP switch-
es.
The DIP switches are on the side of the inverter. See '10
Connection drawing' no. 7.
N.B.: The Power Save Mode can be switched on or off using a
remote control panel whatever the setting of the DIP switches.
S1
S2
Function
OFF
OFF
DC/AC OUT MODE
DC/AC + POWER SAVING
OFF
ON
MODE
UPS MODE + POWER SAVE
ON
OFF
MODE
UPS MODE + DELAY MODE
ON
ON
+ POWER SAVE MODE
S3
S4
Output voltage
OFF
OFF
240 V
ON
OFF
230 V
OFF
ON
220 V
ON
ON
200 V
Inverter type IV60012, IV60024, IV100012, IV100024, IV150012, IV150024, IV200012, IV200024, IV300012, IV300024
Position of
Shore power
switching
present?
relay
YES
1
NO
1
YES
1
NO
1
YES
0
NO
1
YES
0
1
NO
Inverter
Output fre-
S5
quency
OFF
60 Hz
ON
50 Hz
Switching time
Output voltage
if shore power
supplied by:
Inverter
Inverter
Inverter
Inverter
Shore power
Inverter
Walspanning
Shore power
Swichting relay
ENGLISH
Power Save
function
fails
n/a
Switched off
n/a
Switched on
10 msec
Switched on
5 sec
Switched on
15
090134.01