Alpha Technologies PE6500/00 Manuel D'installation page 6

Table des Matières

Publicité

PLACE OF THE BATTERIES
NP7 - 12 12V , 7.0 Ah
NP7 - 12 12V , 7.0 Ah
36V - 2 x 7Ah in parallel
CONNECTIONS
PE6500/00 : delivered with the unit : one complete -36V WCS and 4 wires with terminals
* OPEN THE BREAKER ( handle down )
* PLACE FIRST THE BATTERIES VERTICALLY IN THE RACK
* MAKE ALL CONNECTIONS USING THE -36V WCS ( Wire Cord Set )
* LAY DOWN THE BATTERIES
* PLACE AND FIX THE COVER ( 9 x Torx Combi M3x6 )
* DO NOT CONNECT THE EXTERNAL CABLE
* CLOSE THE BREAKER
* CHECK THE BATTERY VOLTAGE DIRECTLY ON THE REAR CONNECTOR
* OPEN THE BREAKER AND CONNECT THE EXTERNAL CABLE
* CLOSE THE BREAKER
RED
Remove the insulation
for 2 battery strings
YELLOW
BLACK
- 36V - 1 x 7Ah
Alpha Technologies
Belgium
6 / 21
-36V CONFIGURATION
NP7 - 12 12V , 7.0 Ah
NP7 - 12 12V , 7.0 Ah
Do not place the
2 cables in the
battery pack
Battery Pack
PE6500/00/10
36V - 1 x 7Ah
RED
YELLOW
BLACK
- 36V - 2 x 7Ah in parallel
4804 872 46975
February 2012
5 /5
NP7 - 12 12V , 7.0 Ah
NP7 - 12 12V , 7.0 Ah

Publicité