Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

CONNECTIONS
Control output for
channel selector
Connection to
interface module
(cable 9404 407 50011)
a
Mains
(230/115/24)
The Digital 380 indicator is provided for installation in an enclosure. The electrical
safety is reached by correct installation in a control cabinet/panel.

ELECTRICAL CONNECTIONS

Keep mains cables separate from signal and measuring cables. We recommend
twisted and sceened measuring cables (screen connected to earth).
This ensures optimum interference suppression!
Connected final elements must be equipped with protective circuits to manufacturer
specification. This avoids voltage peaks which can cause trouble to the instrument.
The instruments must be protected by an individual or common fuse for a max.
power consumption of 8VA per unit (standard fuse ratings, min 1 A)!.
a
Signal and measurement circuits may carry max. 50 V r.m.s. against
ground,mains circuits may carry max. 250 V r.m.s. between terminals
9499-040-24701
Control inputs
d2
L2
L1
Limit contact
L2
Limit contact
L1
Protective
earth
K
d1
0(4) ... 20mA
K K
Protective earth
0 ... 10V , 5V
0%
0/4 ... 20 mA
100%
Transducer
+
PT100,resistance
+
ß 1V
Thermo
couples
+U T
2-wire transmitter
supply
Analog output
3

Publicité