Led Indicators; Technical Data - Vetus IVPS Manuel D'utilisation Et Instructions D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 10
5
Operation
The Automatic change over device switches automatically
between the three AC sources.
The input is taken from output of Generator, Shore Power and
Inverter. In case of failure of generator the shore power will take-
over. If shore power and generator fail, inverter will take over.
The Vetus IVPS has a built-in micro controller to control the
relays and indicators. The micro controller is used to choose
the best source of power based on two choices: the prior-
ity of the power source, and the voltage of the power source.
For example, if the shore power and generator are both avail-
able, the generator power will have priority. But if the voltage of
the generator power is too low or too high, then the priority of
the generator is not considered, and the shore power is used.
The acceptable voltage of the shore power and generator is
230 V AC –20% and +10%. This means the voltage must be
between 184 V and 253 V.
6
Malfunctions
Malfunction /indication
LED 'Generator IN' off
LED 'Shore power IN' off
LED 'Inverter IN' off
LED 'Generator IN' on,
But output powered from Shore
Power
LED 'Shore power' on But
output powered from the
inverter.
7
Technical data
Type
Function
Capacity
Nominal voltage
Accepted voltage of generator and shore power
Frequency
Time delay
Dimensions
Weight
Automatic change-over device type IVPS
Possible cause
No output from the generator.
Connection fault.
LED printed circuit board connection
broken.
No output from the shore power.
Connection fault.
No output from the inverter.
Connection fault.
Generator output voltage is not within
the limits (too low or high)
Module fault.
Shore power output voltage is not
within the limits (too low or high)
Module fault.
: IVPS
: Automatic switching system between generator or shore power or Inverter
: 4.5 kVA maximum
: 230V AC
: -20% and +10% (higher than 184 V, lower than 253 V
: 50Hz
: Switching delay to generator mode is adjustable between 1-30 Sec
: 290 x 180 x 95 mm
: 2.4 kg
In case the output is switched to shore power or inverter and the
generator is switched-on (manual) a delay can be a set to give
the generator time to start-up. Generator time delay is adjustable
from 1 to 30 seconds.
5.1. LED indicators
LED
Generator IN
ON:
Generator OUT
ON:
Shore Power IN
ON:
Shore Power OUT
ON:
Inverter IN
ON:
Inverter OUT
ON:
Solution
Switch ON the generator and check the output.
Check the connections of the generator to IVPS.
Contact service department.
Switch ON the shore power and check the output.
Check the connections of the shore power to IVPS.
Switch ON the inverter and check the output.
Check the connections of the inverter to IVPS.
Check voltage of the generator.
Contact service department.
Check the voltage of the shore power.
Contact service department.
      ENGLISH
FUNCTION
Generator is ON
Output powered by generator
Shore Power is ON
Output powered by shore
power
Inverter is ON
Output powered by inverter
090131.01
7

Publicité

Table des Matières
loading

Table des Matières