5.2 Stop (without environment thermostat)
- Place the main switch to OFF.
- Combustion halts while the fan continues to cool the interior of the generator for 3 minute.
5.3 Start (with environment thermostat)
- The unit is pre-set for connection to an environment thermostat (not supplied as standard).
- Connection should be made using the plug on the control panel.
- Having set the environment thermostat, place the switch to AUT. To halt the generator,
operate either the main switch or the environment thermostat.
In both cases, the generator undergoes a correct cooling cycle.
6.
MAINTENANCE
The maintenance intervals recommended in this manual refer to generator operation
of 8 ÷ 10 hours/day.
- Every month: clean the photosensitive cell, the ignition electrodes and the flame turbo.
- Every three months or every 300 hours of operation, replace the filters of the diesel.
- Every 6 months: clean the fuel tank.
Cleaning the turbo :
- Remove the fuel oil pipe.
- Slide out the photosensitive cell and the HT leads from the electrodes.
- Unscrew the two screws securing the head to the boiler (the head is removed complete).
N.B. - When refitting the combustion head after cleaning operations, make sure that the relative
position between the nozzle and the electrodes must be respected, as shown in the scheme
at the end of the manual.
GB
4