Télécharger Imprimer la page

Publicité

Liens rapides

All manuals and user guides at all-guides.com
INSTALLATION MANUAL
KPAFP125R5IA-
KPAFP165R5IA-
KPAFP185R5IA-
Split system air conditioner
37.4163.267.0
MARZO 2005

Publicité

loading

Sommaire des Matières pour Technibel KPAFP125R5IA Serie

  • Page 1 All manuals and user guides at all-guides.com INSTALLATION MANUAL KPAFP125R5IA- KPAFP165R5IA- KPAFP185R5IA- Split system air conditioner 37.4163.267.0 MARZO 2005...
  • Page 2 All manuals and user guides at all-guides.com IMPORTANT! Please Read Before Starting When Installing… …In a Room This air conditioning system meets strict safety and operat- ing standards. As the installer or service person, it is an Properly insulate any tubing run inside a room to prevent important part of your job to install or service the system so it “sweating”...
  • Page 3 All manuals and user guides at all-guides.com Check of Density Limit 2. The standards for minimum room volume are as follows. The room in which the air conditioner is to be (1) No partition (shaded portion) installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit.
  • Page 4 All manuals and user guides at all-guides.com CONTENTS Page Page IMPORTANT ......2 4-2.
  • Page 5 All manuals and user guides at all-guides.com 2. DIMENSIONS (mm) Center of tubing hole ø 75 (4 places) Wide tube Narrow tube Drain hose ø 26 Unit : mm...
  • Page 6 All manuals and user guides at all-guides.com 3. HOW TO INSTALL THE UNIT Minimum operation and maintenance area. (fig. 4-1) 3000 Fig. 3-2 3000 max 400 Fig. 3-1 Find the place for the installation. The unit can be connec- ted in four different positions: at the right-back side, at the left-back side, at the botton on the right or on the left.
  • Page 7 All manuals and user guides at all-guides.com Drill a 80 mm hole, insert a PVC pipe. (fig. 3-6) Remove the return air grille releasing it from the side guides and the central elastic stop. (fig. 3-7) 5 - 10 mm Open a pre-punched hole for the pipe passage (work from Fig.
  • Page 8 All manuals and user guides at all-guides.com 4. ELECTRICAL WIRING 4-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit (7) Regulations on wire diameters differ from locality as shown on its nameplate, then carry out the to locality.
  • Page 9 All manuals and user guides at all-guides.com 4-3. Wiring System Diagrams Indoor unit (No. 1) Outdoor unit Power supply INV unit 220-240V 50Hz Power supply 200-240V 50Hz Ground Remote controller Ground Ground Indoor unit (No. 2) Power supply 220-240V 50Hz Ground Ground Indoor...
  • Page 10 All manuals and user guides at all-guides.com CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units.
  • Page 11 All manuals and user guides at all-guides.com (5) Use shielded wires for inter-unit control wiring (c) and ground the shield on both sides, other- wise misoperation from noise may occur. (Fig. 4-4) Connect wiring as shown in Section “4-3. Shielded wire Wiring System Diagrams.”...
  • Page 12 All manuals and user guides at all-guides.com 5. HOW TO PROCESS TUBING Deburring The narrow tubing side is connected by a flare nut, After Before and the wide tubing side is connected by brazing. 5-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units.
  • Page 13 All manuals and user guides at all-guides.com Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Apply refrigerant lubricant here and here (2) Be sure to apply refrigerant lubricant to the match- ing surfaces of the flare and union before connect- Fig.
  • Page 14 All manuals and user guides at all-guides.com Do not use a spanner to tighten the valve stem Packed valve Charging port caps. Doing so may damage the valves. Depending on the installation conditions, applying excessive torque may cause the nuts to crack. Valve stem Precautions for Packed Valve Operation If the packed valve is left for a long time with the...
  • Page 15 All manuals and user guides at all-guides.com 5-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To pre- vent the condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing.
  • Page 16 All manuals and user guides at all-guides.com 6. SPECIAL REMARKS I HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER K70D038ZAA Installing the Control Unit Fix the operation controller on the metal plate near the Elec. Junction Box. Use the provided screws. Connect the wireless controller 6 poles wire group with the one coming from indoor unit receiver.
  • Page 17 All manuals and user guides at all-guides.com 7. APPENDIX Care and Cleaning 1. For safety, be sure to turn the air conditioner off and also to disconnect the power before cleaning. 2. Do not pour water on the indoor unit to clean it. This will damage the internal components and cause an electric shock hazard.
  • Page 18 All manuals and user guides at all-guides.com Troubleshooting If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or a service center. Trouble Possible Cause Remedy Air conditioner does not run at all.
  • Page 19 All manuals and user guides at all-guides.com Entretien et nettoyage 1. Pour toute sécurité, éteignez le climatiseur et débranchez-le de la AVERTISSEMENT prise secteur. 2. Ne versez pas d’eau sur l’unité intérieure pour la nettoyer. Cela pourrait abîmer les composants internes et provoquer des décharges électriques.
  • Page 20 All manuals and user guides at all-guides.com Guide de dépannage Si le climatiseur ne fonctionne pas correctement, effectuez les vérifications suivantes avant de faire appel à un réparateur. Si le problème persiste, prenez contact avec votre concessionnaire ou avec un service après-vente. Panne Cause possible Remède...
  • Page 21 All manuals and user guides at all-guides.com Pflege und Reinigung 1. Aus Sicherheitsgründen darauf achten, das Gerät vor dem Reinigen WARNUNG auszuschalten und es außerdem vom Netz zu trennen. 2. Kein Wasser auf die Inneneinheit schütten, um diese zu reinigen. Dadurch werden die inneren Bauteile beschädigt, und es besteht Stromschlaggefahr.
  • Page 22 All manuals and user guides at all-guides.com Fehlersuche Wenn Ihr Klimagerät nicht richtig funktioniert, zuerst die folgenden Punkte überprüfen, bevor ein Kundendiensttechniker angefordert wird. Läßt sich die Störung nicht beheben, so wenden Sie sich bitte an Ihren Fachhändler oder an eine Kundendienststelle. Störung Mögliche Ursache Abhilfe...
  • Page 23 All manuals and user guides at all-guides.com Cura e manutenzione 1. Per motivi di sicurezza, accertare che il condizionatore d’aria sia AVVERTIMENTO spento e che la spina del cavo di alimentazione sia staccata dalla presa di corrente prima di procedere con le operazioni di pulizia. 2.
  • Page 24 All manuals and user guides at all-guides.com Prima di chiamare il tecnico Se il condizionatore d’aria non funziona correttamente, prima di chiamare il tecnico per la riparazione controllare quanto segue. Se ciò non consente di eliminare il problema, rivolgersi al proprio rivenditore o centro di assistenza. Problema Causa probabile Rimedio...
  • Page 25 All manuals and user guides at all-guides.com Cuidados e limpeza 1. Por motivos de segurança desligue o aparelho de ar condicionado e ADVERTÊNCIA desligue-o também da rede antes de proceder à sua limpeza. 2. Não verta água sobre a unidade interior para a limpar. Poderá danificar os componentes internos e causar descargas eléctricas.
  • Page 26 All manuals and user guides at all-guides.com Resolução de problemas Se o seu aparelho de ar condicionado não funciona correctamente, verifique primeiro os seguintes pontos antes de solicitar assistência. Se não conseguir solucionar o problema, contacte o seu concessionário ou o serviço de assistência.
  • Page 27 All manuals and user guides at all-guides.com Φροντίδα και καθάρισµα 1. Για λόγους ασφαλείας, πριν από το καθάρισµα, πρέπει να σβήνετε τη συσκευή κλιµατισµού και βγάζετε το ηλεκτρικό καλώδιο από την πρίζα. 2. Μη ρίχνετε νερό στην εσωτερική µονάδα για να την καθαρίσετε. Αυτό...
  • Page 28 All manuals and user guides at all-guides.com Αντιµετώπιση προβληµάτων Αν το κλιµατιστικό σας δεν λειτουργεί σωστά, ελέγξτε πρώτα τα ακόλουθα σηµεία πριν ζητήσετε κάποια εργασία επισκευής. Αν η συσκευή συνεχίζει να µη λειτουργεί σωστά, ειδοποιήστε τον προµηθευτή σας ή το κέντρο εξυπηρέτησης. Πρόβληµα...
  • Page 29 All manuals and user guides at all-guides.com Cuidados y limpieza 1. Por motivos de seguridad, asegúrese de apagar el acondicionador ADVERTENCIA de aire, y desconectarlo también de la red eléctrica antes de realizar su limpieza. 2. No vierta agua sobre la unidad interior para limpiarla. El agua podría estropear los componentes internos y producir una descarga eléctrica.
  • Page 30 All manuals and user guides at all-guides.com Localización de averías Si su acondicionador de aire no funciona correctamente, compruebe primero la lista de abajo antes de llamar al servicio de reparaciones. Si no puede solucionar el problema, póngase en contacto con su concesionario o centro de reparaciones.
  • Page 31 All manuals and user guides at all-guides.com...
  • Page 32 All manuals and user guides at all-guides.com In order to carry on a constant improvement, our products can be modified without prior notice. Per garantire un costante miglioramento dei nostri prodotti, ci riserviamo di modificarli senza preavviso. Par souci d’amélioration constante, nos produits peuvent être modifiés sans préavis. Unsere Produkte werden laufend verbessert und können Vorankündigung abgeändert Werden.

Ce manuel est également adapté pour:

Kpafp165r5ia serieKpafp185r5ia serie