INSTALLATION INSTRUCTIONS
E-APE Series
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety
precautions should always be followed including the
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This Product Must Be Installed In Accordance With The
Applicable Installation Code By A Person Familiar With
The Construction And Operation Of The Product And
The Hazards Involved.
Ce Produit Doit Être Installé Selon Le Code D'installation
Pertinent, Par Une Personne Qui Connaît Bien Le
Produit Et Son Fonctionnement Ainsi Que Les Risques
Inhérents.
3.
Min. 75°C supply conductors.
Les fils d'alimentation 75°C min.
4.
Suitable for wet locations.
Convient aux emplacements mouilles.
5.
Downlight only.
Downlight seulement.
6.
Mounting height no less than 12 feet from the ground.
SAVE THESE INSTRUCTIONS
FOR FUTURE REFERENCE
U-BRACKET MOUNTING
NOTE: Fixture is only UL listed for downlight orientation.
NOTE: Use this fixture installation sheet for installing. DO NOT refer
to the mounting accessory sheet for installation.
1. Loosen (2) screws on driver door of the fixture and open driver
access door.
2. Attach U-bracket to fixture housing as shown in Figure 1. Make sure
sealing washers are under bolt heads.
NOTE: Be sure mounting holes in U-bracket are offset from center
line of U-bracket in the same directions as the holes are offset in
fixture.
following:
www.e-conolight.com
Document:
LPN00607X0001A0_B
Created By:
TMT
3. Pass bolts (with sealing washers in place) through wall of fixture and
U-bracket. Bolt heads must be on inside of fixture housing.
4. Slide (2) lock washers over bolts.
5. Secure U-bracket to fixture with (2) 5/16 nuts. Tighten nuts to
132 in-lbs (15 N·m).
6. Insert end of cord supplied with U-bracket kit through cord grip so
that the leads extend from the threaded end of the cord grip by
approximately 4". Tighten cord grip firmly to cord.
7. Remove nut from cord grip. Pass threaded end of cord grip through
wall of fixture from outside to inside of the fixture. Make sure gasket
for cord grip is against the outside wall of the fixture.
8. Tighten nut on threaded end of cord grip to secure cord grip to fixture.
Do not over tighten nut to prevent damage to threads.
9. Connect cord green wire to fixture ground wire (green). Connect
cord white to fixture common wire (white). Connect cord black wire to
fixture voltage wire (black).
10. Close driver door and retighten (2) screws loosened in Step 1 above.
11. Mount fixture using (2) 3/8 (10 mm) bolts and washers appropriate for
the mounting surface. See Figure 2.
12. Make wiring connections to cord leads per the Electrical
Connections section.
13. Use the adjustment screw provided in hardware bag to secure the
U-bracket in a fixed position. Securely tighten both center bolts on
the sides of the U-bracket.
FIGURE 1
Adjustment Screw and Holes
Hex Nuts
Cord
Outer Trunion
FIGURE 2
|
888.243.9445
|
FAX: 262.504.5409
Date
ECO#
Align these
Two Trunion Holes
Gasket for
Cord Grip
Cord Grip
Sealing Washers
Lock
Washers
Lock Washer
between Trunions
Nut for
Cord Grip
Inner Trunion
(Assembles to the Housing)
9-16-2019
011017
Hex Bolts
Back Box