INSTALLATION INSTRUCTIONS Blitzductor
Installation / Montage
Blitzductor BXT BAS EX
IECE DEK 11.0078X
Ex ia [ia Ga] IIC T4/T5/T6 Gb
Ex ib IIC T4/T5/T6 Gb
KEMA 06 ATEX 0274 X
OCP 0004
II 2 (1) G Ex ia [ia Ga] IIC T4/T5/T6 Gb
II 2 G Ex ib IIC T4/T5/T6 Gb
Certificado N.º: TUV 17.0697X
FISCO
Ex ia [ia Ga] IIC T6...T4 Gb
Standards:
Ex ib IIC T6...T4 Gb
for ATEX: EN 60079- 0: 2012
Para conexão para circuitos
EN 60079-11: 2012
intrinsecamente:
for IECEx: IEC 60079-0:
2011
U
= 30 V
i
IEC 60079-11: 2011
I
= 500 mA
i
IEC 60079-26: 2006
P
= indeterminada
i
Connection with intrinsically
C
= desprezível
i
safe circuits with:
L
= desprezível
i
U
= 30 V
i
Ou para conexão para circuitos
I
= 500 mA
i
FISCO
P
= any
i
U
= 17,5 V
i
C
negligibly small
i
I
= 380 mA
L
negligibly small
i
i
P
= 5,32 W
i
Special conditions for safe use
C
= desprezível
i
The dielectric strength of at least 500 V of
L
= desprezível
i
the intrinsically safe circuits of the
Faixa de temperatura ambiente:
Blitzdutor series BXT is limited only by the
-40 °C ≤ Ta ≤ +55 °C – para T6
overvoltage protection. For Blitzductor
-40 °C ≤ Ta ≤ +75 °C – para T5
BXT series type BXT ML2 BD S EX 24, the
-40 °C ≤ Ta ≤ +80 °C – para T4
terminals X3, X4, X3' and X4' are
considered to be connected to earth.
Normas Técnicas / Regulamento:
ABNT NBR IEC 60079-0:2013
Ambient temperature range:
-40°C... +55°C for temperature class T6
ABNT NBR IEC 60079-11:2013
ABNT NBR IEC 60079-26:2016
-40°C... +75°C for temperature class T5
Portaria INMETRO n° 179 de 18/05/2010
-40°C... +80°C for temperature class T4
Basic circuit diagram / Prinzipschaltbild
0.08 - 2.5 mm²
□
AWG 28 -14
7 mm
≤ 0.4
≤ 3.5
Nm
in-lbs
2.5
0.4
mm
mm
Fieldbus FISCO
Power supply
U o ≤ 17.5 V,
I o ≤ 380 mA
1
Field device
U i ≤ 17.5 V, I i ≤ 380 mA,
P i ≤ 5.32 W, C i negligibly small,
L i negligibly small
protected
terminal 4
terminal 3
*) direct shield earthing
Direkte Schirmerdung
BXT ML2 BD S EX 24
terminal 2
terminal 1
®
BXT ML2 BD S EX 24
BXT ML2 BD S EX 24
I
L
≥ 4 mm²
□
≤ AWG 10
1
Power supply (Fisco); Segment
2
Blitzductor BXT ML2 BD EX 24
Field device (Fisco)
3
Terminator
**)
Segment
2
*)
2
**)
protected
**) indirect shield earthing
(only in case of BXT ML2 BD S EX 24)
Indirekte Erdung des Schirmleiters
(nur bei BXT ML2 BD S EX 24 möglich)
1
Connection / Anschluss
protected
protected
protected
2
3
terminal 1
terminal 2
terminal 3
terminal 4
1791 / 08.17 / 3009207
2
4
1
1 2 3 4
4´ 3´ 2´ 1´
1
3
BXT BAS EX
BXT ML2...
2
2
4
1 2 3 4
4´ 3´ 2´ 1´
1
3
BXT BAS EX
BXT ML2 BD S EX 24, 920 280
1
2
3
4
Note:
Use Test Device
not in
hazardous area!
© COPYRIGHT 2017 DEHN + SÖHNE protected by ISO 16016
2´
4´
1´
3´
2´
4´
1´
3´
1´
2´
protected
3´
4´
www.dehn.de
www. dehn-international.com