INSTALLATION GUIDE
5 Series
10-15 Tons Hydronic Heat Pump
R-454B /
60Hz
General Installation Information ................................................................................................ 2
Nomenclature ................................................................................................................................... 5
Water Quality ................................................................................................................................... 8
Field Connected Water Piping ................................................................................................... 9
Flow Rate ........................................................................................................................................... 11
Typical Application Piping .......................................................................................................... 12
Electrical Data .................................................................................................................................. 13
Dimensional Data ............................................................................................................................ 14
Physical Data .................................................................................................................................... 15
Reference Calculations ................................................................................................................. 15
HydroZone Controller ................................................................................................................... 16
Unit Startup ....................................................................................................................................... 24
Refrigerant Removal and Evacuation ..................................................................................... 26
Charging Procedures ..................................................................................................................... 26
Refrigerant Recovery..................................................................................................................... 27
Revision Guide ................................................................................................................................. 29
WARNING: Before performing service or maintenance
operations on the system, turn off main power switches
to the unit. Electrical shock could cause serious personal
injury.
WARNING: All products are designed, tested, and
manufactured to comply with the latest publicly released
and available edition of UL 60335-2-40 for electrical
safety certification. All field electrical connections must
follow the National Electrical Code (NEC) guide standards
and / or any local codes that may be applicable for the
installation.
WARNING: Only factory authorized personnel are
approved for startup, check test and commissioning of
this unit.
INSTALLER: Please take the time to read and understand
these instructions prior to any installation. Installer must
give a copy of this manual to the owner.
Definition of Warnings and Symbols
DANGER
WARNING
CAUTION
NOTICE
WARNING
Indicates a situation that results in death or
serious injury.
Indicates a situation that could result in
death or serious injury.
Indicates a situation that could result in
minor or moderate injury.
Indicates a situation that could result in
equipment or property damage.
For the User
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have
been given supervision or instruction concerning use of the
appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play
with the appliance.
Keep this manual in a safe place in order to provide your
service personnel with necessary information.
NOTICE
NOTICE: To avoid equipment damage, do not leave the system
filled in a building without heat during cold weather, unless
adequate freeze protection levels of antifreeze are used. Heat
exchangers do not fully drain and will freeze unless protected,
causing permanent damage.
IGW5-0026W
WARNING

Publicité

loading

Sommaire des Matières pour Water Furnace 5 Serie

  • Page 1 INSTALLATION GUIDE 5 Series 10-15 Tons Hydronic Heat Pump R-454B / 60Hz IGW5-0026W General Installation Information ....................2 Nomenclature ........................... 5 Water Quality ........................... 8 Field Connected Water Piping ....................9 Flow Rate ............................11 Typical Application Piping ......................12 Electrical Data ..........................
  • Page 2 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information NOTICE: Do not store or install units in corrosive environments sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including ciga- or in locations subject to temperature or humidity extremes.
  • Page 3 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information Installation Space Requirements WARNING Ventilated Area: ensure that the area is in the open or that it NOTE: Equipment with refrigerant charge less than 62 oz does is adequately ventilated before breaking into the system of not require have a minimum floor area requirement and does not conducting any hot work.
  • Page 4 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information WARNING Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.
  • Page 5 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information Model Nomenclature Brand Brand W – WFI W – WFI IntelliStart 0 – None Model Model 1 – Yes 5 – 5 Series 5 – 5 Series Mitigation Type Type 0 –...
  • Page 6 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information - Serial Plate Example Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min. distance to combustible surface (in/cm) Max.
  • Page 7 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE General Installation Information Safety Considerations Unit Location Installing and servicing air conditioning and heating Provide sufficient room to make water and electrical equipment can be hazardous due to system pressure and connections. If the unit is located in a confined space, electrical components.
  • Page 8 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Water Quality General The following table outlines the water quality guidelines for unit heat exchangers. If these conditions are exceeded, a secondary Two-Stage Hydronic systems may be successfully applied heat exchanger is required. Failure to supply a secondary heat in a wide range of residential, commercial, and industrial exchanger where needed will result in a warranty exclusion for applications.
  • Page 9 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Field Connected Water Piping General Water Flow Rate The proper water flow must be delivered to each unit Each unit is equipped with captive 2 in. [50.8 mm] FPT water whenever the unit heats or cools. To assure proper flow, connections to eliminate ‘egg-shaping’...
  • Page 10 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Field Connected Water Piping cont. Closed Loop Tower/Boiler Systems The water loop is usually maintained between 60°F [15.5°C] and 90°F [32.2°C] for proper heating and cooling operation. This is accomplished with a cooling tower and a boiler. To reject excess heat from the condenser water loop, the use of a closed-circuit evaporative cooler or an open type cooling tower with a secondary heat exchanger between...
  • Page 11 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Flow Rate Load Flow Rate Source Flow Rate The load flow on all water to water products including The source flow can range between 2.25 and 3 gpm per the Two-Stage Hydronic Series should be 3 gpm per ton ton for earth loops.
  • Page 12 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Typical Application Piping 30 PSI Pressure RELIEF VALVE Gauge Pressure Vent Reduction LOAD PUMP HYDRONIC LOAD Separator Back Flow Preventer / Expansion Pressure Pressure Relief Valve Tank Reduction Dielectric Unions STORAGE TANK WaterFurnace Unit NDW Series Hose Kit...
  • Page 13 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Electrical Data Load Source Total Compressor* Supply Rated Voltage Model Pump Pump Unit Circ Fuse/ Circuit Voltage Min/Max HACR LRA** 208-230/60/1 187/253 47.0 30.1 170.0 59.5 30.1 37.6 L1/L2 208-230/60/1 187/253 47.0 30.1 170.0 59.5 38.5...
  • Page 14 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Dimensional Data 120-180 - Top Waterline Configuration 25.58 OPTIONAL TOP WATER FRONT CONNECTIONS LOAD PRIMARY 33.60 SERVICE ACCESS CONTROL BOX 5.82 WATERLINES BACK LOCATION 5.28 BACK CONTROL BOX 21.07 2.26 2.26 SOURCE 2' ALTERNATE SERVICE ACCESS 24.01 LOW VOLTAGE...
  • Page 15 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Physical Data Model Compressor (2 each) Factory Charge R-454B, oz [kg] 40 [1.13] 46 [1.30] Load Water Connection FPT - in Source Water Connection FPT - in Weight - Operating, lb [kg] 400 [181] 420 [190] Weight - Packaged, lb [kg] 395 [179]...
  • Page 16 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions Installation Instructions The HydroZone controller is a part of the hydronic heat pump system. The part number for this product is HZC. This controller is a human interface and water tank control device. The controller displays and regulates the water tank temperature, but not the conditioned space.
  • Page 17 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. Backlight on Time This controller has a two color backlight feature. Anytime a button is pressed, the blue backlight stays on for a certain amount of time. A red backlight is visible if you are selecting Emergency Heat mode. You can adjust the amount of time the backlight stays on in the menu options.
  • Page 18 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. Main Screen After exiting from the setup mode, controller displays the main screen. OPERATION, displays the current controller setup selection. They are OUTDOOR, TANK CONTROL AUTO, and TANK CONTROL MANUAL MODE.
  • Page 19 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. Wiring Schematic NDW Unit 1 Compr essor 2 Compr essor 2 O-C2 O-C2 Relay C2 Relay C2 Relay C2 Relay C2 Green (C4 ) Y-C2 Y-C2 Gray (C3) Compressor 1 Compressor 1 Blue (C2) R-C2...
  • Page 20 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. All these temperature settings are with increments of 1°F. The dead band is 2°F to 15°F with increments of 1°F. Tank Temperature Set point is calculated internally by the outdoor reset algorithm, and updated every 30 minutes if this setup is selected.
  • Page 21 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. If no heating is selected, the screen shall go to the COOLING screen. If cooling fixed is selected, the default temperature for tank setpoint is 80°F with a 10°F deadband. The set range is 40°F to 85°F, with increments of 1°F.
  • Page 22 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE HydroZone Controller Instructions cont. If AUX is selected in stage 4, ENTER would take the user to “ADDITIONAL DEAD BAND FOR AUX HEAT” screen and then to “MAXIMUM OAT FOR AUX HEAT” screen. The “ADDITIONAL DEAD BAND FOR AUX HEAT”...
  • Page 23 HydroZone Controller Instructions cont. Service Contact Information Input dealer info. INPUT DEALER INFO DEALER INFO BRAND NAME BRAND NAME: MODEL NUMBER TO SCORLL THRU CHARACTERS SERIAL NUMBER WATER FURNACE CONTRACTOR NAME ------------- CONTRACTOR PHONE SAVE SELECT OPTION CHANGE LETTER PREVIOUS ENTER PREVIOUS ENTER...
  • Page 24 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Unit Startup Verify the following: Configuring the Sensor Kits • High voltage is correct and matches nameplate The Aurora Advanced Control allows Refrigeration, Energy, • Fuses, breakers and wire size are correct and Performance Monitoring sensor kits. The following •...
  • Page 25 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Unit Startup cont. Refrigerant Monitoring Startup Steps (Standard Sensor Kit) • Set thermostat control above cooling setpoint. The Refrigerant Monitoring Kit for compressors A and B • Set thermostat control in cooling mode. includes two pressure transducers, and three temperature •...
  • Page 26 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Refrigerant Removal and Evacuation This process might need to be repeated several times. Com- When breaking into the refrigerant circuit to make repairs – or for any other purpose conventional procedures shall be used. pressed air or oxygen shall not be used for purging refriger- However, for flammable refrigerants it is important that best ant systems.
  • Page 27 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Refrigerant Recovery When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available.
  • Page 28 10-15 TONS HYDRONIC HEAT PUMP INSTALLATION GUIDE Notes...
  • Page 29 Revision Guide Pages: Description: Date: Document Creation 23 Sept 2024...
  • Page 30 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com Product: 5 Series Type: Hydronic Heat Pump Size: 10-15 Ton Document: Installation Guide *IGW5-0026W* ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy IGW5-0026W 12/24 of continual product research and development and reserves the right to change design and specifi...
  • Page 31 MANUEL D’INSTALLATION Série 5 Thermopompe hydronique de 10 à 15 tonnes R-454B/ 60 Hz IGW5-0026W Informations générales sur l’installation ................2 Nomenclature ........................... 5 Qualité de l’eau ..........................8 Tuyauterie d’eau raccordée sur place ..................9 Débit ..............................11 Tuyauterie d’application type ....................12 Données électriques ........................
  • Page 32 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Informations générales sur l’installation AVIS : N’installez pas les unités dans un environnement corrosif Si des travaux à chaud doivent être effectués sur le matériel de réfrigération ou toute pièce associée, un matériel d’extinction ou dans des endroits soumis à...
  • Page 33 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Informations générales sur l’installation Site d’installation AVERTISSEMENT Cet équipement a été évalué pour être installé à une altitude • L’appareil devrait être entreposé de manière à prévenir les maximale de 3 000 m (9 843 pi) et ne doit pas être installé dommages mécaniques et dans un local bien ventilé...
  • Page 34 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Informations générales sur l’installation AVERTISSEMENT Prenez les précautions suffisantes en cas de fuite de réfrigérant. En cas de fuite de gaz réfrigérant, ventilez immédiatement la zone. RISQUES POSSIBLES : Des concentrations excessives de réfrigérant dans une salle fermée peuvent entraîner un manque d’oxygène.
  • Page 35 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Informations générales sur l’installation Model Nomenclature Brand Brand W – WFI W – WFI IntelliStart 0 – None Model Model 1 – Yes 5 – 5 Series 5 – 5 Series Mitigation Type Type...
  • Page 36 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Renseignements généraux sur l’installation – Exemple de plaque de série Unit Nomenclature and Serial Number Unit Voltage Max Fuse Fuse/Breaker Size Time Delay Component Qty LRA RLA/MRC FLA HP KW Component Electrical Information Min.
  • Page 37 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Informations générales sur l’installation Considérations de sécurité Emplacement de l’unité L’installation et l’entretien des appareils de climatisation Prévoyez un espace suffisamment grand pour effectuer les et de chauffage peuvent être dangereux en raison de la raccords d’eau et d’électricité.
  • Page 38 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Qualité de l’eau Généralités Le tableau suivant présente les recommandations relatives à la qualité de l’eau pour les échangeurs de chaleur des unités. Les systèmes hydroniques à deux phases peuvent être Si ces conditions sont dépassées, un échangeur de chaleur utilisés avec succès dans une vaste gamme d’applications secondaire est requis.
  • Page 39 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Tuyauterie d’eau raccordée sur place Généralités Débit d’eau Le bon débit d’eau doit être acheminé à chaque unité Chaque unité est équipée de raccords d’eau FPT captif de chaque fois qu’elle chauffe ou refroidit. Pour assurer un 50,8 mm (2 po) pour éliminer la « formation d’œufs »...
  • Page 40 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Tuyauterie d’eau raccordée sur place (suite) Systèmes de tour/chaudière en boucle fermée La boucle d’eau est généralement maintenue entre 15,5 à Valves 32,2 °C (60 à 90 °F) pour assurer le bon fonctionnement du à...
  • Page 41 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Débit Débit de la charge Débit de la source Le débit de la charge de tous les produits eau-eau, dont la Le débit de la source peut varier entre 8,52 et 11,36 L/min/t série hydronique à...
  • Page 42 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Tuyauterie d’application type SOUPAPE DE DÉCHARGE DE 2,1 bar (30 lb/po2) Manomètre Évent Réduction de d’aération la pression POMPE DE CHARGE CHARGE HYDRONIQUE Séparateur d’air Dispositif antirefoulement/ Vase Réduction Soupape de décharge d’expansion de la pression Raccords unions...
  • Page 43 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Données électriques Pompe Pompe Total Amp . Fusible Compresseur* Circuit Tension Tension Modèle min. max./ d’alimentation nominale min./max. charge source l’unit. du cir. HACR LRA** 208-230/60/1 187/253 47,0 30,1 170,0 59,5 30,1 37,6...
  • Page 44 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Données dimensionnelles 120-180 - Top Waterline Configuration 25.58 OPTIONAL TOP WATER FRONT CONNECTIONS LOAD PRIMARY 33.60 SERVICE ACCESS CONTROL BOX 5.82 WATERLINES BACK LOCATION 5.28 BACK CONTROL BOX 21.07 2.26 2.26 SOURCE 2' ALTERNATE...
  • Page 45 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Données physiques Modèle Compresseur (2 chacun) Charge d’usine R-454B, kg (oz) 1,13 (40) 1,30 (46) Raccord d’eau de charge FPT – po 50,8 (2) 50,8 (2) Raccord de l’eau de source FPT –...
  • Page 46 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone Instructions d’installation Le contrôleur HydroZone fait partie du système de thermopompe hydronique. Le numéro de pièce de ce produit est HZC. Ce contrôleur est une interface humaine et un dispositif de commande de réservoir d’eau.
  • Page 47 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Rétroéclairage de l’heure Ce contrôleur a une fonction de rétroéclairage deux couleurs. Chaque fois qu’un bouton est enfoncé, le rétroéclairage bleu reste allumé pendant un certain temps. Un rétroéclairage rouge est visible si vous sélectionnez le mode de chauffage d’urgence. Vous pouvez régler la durée pendant laquelle le rétroéclairage reste allumé...
  • Page 48 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Écran principal Après avoir quitté le mode de configuration, le contrôleur affiche l’écran principal. OPÉRATION, affiche la sélection de configuration actuelle du contrôleur. Ils sont EXTÉRIEUR, COMMANDE AUTO DU RÉSERVOIR et COMMANDE MANUELLE DU RÉSERVOIR.
  • Page 49 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Wiring Schematic NDW Unit 1 Compr essor 2 Compr essor 2 O-C2 O-C2 Relay C2 Relay C2 Relay C2 Relay C2 Green (C4 ) Y-C2 Y-C2 Gray (C3)
  • Page 50 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Tous ces réglages de température sont effectués par incréments de 0,5 à 1 °C (1 °F). La bande morte est de -16,7 à -9,4 °C (2 à 15 °F) par incréments de 0,5 à 1 °C (1 °F). Le point de consigne de température du réservoir est calculé...
  • Page 51 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Si aucun chauffage n’est sélectionné, l’écran doit passer à l’écran REFROIDISSEMENT. Si le refroidissement fixe est sélectionné, la température par défaut pour le point de consigne du réservoir est de 26,6 °C (80 °F) avec une bande morte de -12,2 °C (10 °F).
  • Page 52 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Instructions pour le contrôleur HydroZone (suite) Si AUX est sélectionné à la phase 4, ENTRÉE amènerait l’utilisateur à l’écran « BANDE MORTE SUPPLÉMENTAIRE POUR LE CHAUFFAGE AUXILIAIRE », puis à l’écran « OAT MAXIMALE POUR LE CHAUFFAGE AUXILIAIRE ». La « BANDE MORTE SUPPLÉMENTAIRE POUR LE CHAUFFAGE AUXILIAIRE »...
  • Page 53 Coordonnées du service Saisir les renseignements sur le détaillant. INPUT DEALER INFO DEALER INFO BRAND NAME BRAND NAME: MODEL NUMBER TO SCORLL THRU CHARACTERS SERIAL NUMBER WATER FURNACE CONTRACTOR NAME ------------- CONTRACTOR PHONE SAVE SELECT OPTION CHANGE LETTER PREVIOUS ENTER PREVIOUS ENTER Lorsque l’installateur sélectionne ENTRÉE à...
  • Page 54 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Démarrage de l’unité Vérifier ce qui suit : Configuration des trousses de capteurs • La haute tension est correcte et correspond à la plaque Le système Aurora Advanced Control permet des trousses signalétique.
  • Page 55 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Démarrage de l’unité (suite) Surveillance du fluide frigorigène Étapes de démarrage (Trousse de capteurs standard) • Réglez la commande du thermostat au-dessus du point La trousse de surveillance du réfrigérant pour les de consigne de refroidissement.
  • Page 56 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Retrait et évacuation du réfrigérant Lorsque vous ouvrez le circuit frigorifique pour effectuer des Ce processus devra peut-être être répété plusieurs fois. réparations, ou pour toute autre fin, vous devez suivre les L’air comprimé...
  • Page 57 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Récupération du réfrigérant Lors du retrait du réfrigérant d’un système, que ce soit pour l’entretien ou la mise hors service, il est recommandé de retirer tous les réfrigérants en toute sécurité. Lors du transfert du réfrigérant dans des bouteilles, assurez- vous que seules des bouteilles appropriées de récupération de réfrigérant sont utilisées.
  • Page 58 GUIDE D’INSTALLATION DE LA THERMOPOMPE HYDRONIQUE DE 10 À 15 TONNES Notes...
  • Page 59 Guide de révision Pages Description Date Toutes Création de document 23 septembre 2024...
  • Page 60 Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com Produit : Série 5 Type : Thermopompe hydronique Taille : 10 à 15 tonnes Document : Manuel d’installation *IGW5-0026W* ©2024 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. La politique de WaterFurnace en matière de IGW5-0026W 12/24 recherche et de développement de produits est continue;...