1 - Non repetitive Itsm
is given without voltage
reapplied . This curve is used to define the pro
tection (fuses).
2 - Repetitive Itsm
is given for inrush current with
initial Tj = 70°C. In normal operation, this curve
musn't be exceeded.
Caution, frequent over load currents will
decrease the life expectancy of the SSR.
1 - Itsm non répétitif
sans tension réappliquée est
donné pour la détermination des protections.
2 -Itsm répétitif
est donné pour des surcharges de
courant (Tj initiale=70°C).
Attention : la répétition de ces surcharges de
courant diminue la durée de vie du relais.
Warning ! semiconductor relays don't provide any galvanic insulation between the load and the mains. Always use in
conjunction with an adapted circuit breaker with insulation feature or a similar device in order to ensure a reliable insulation in
the event of wrong function and when the relay must be insulated from the mains (maintenance ; if not used for a long duration
...).
It is important that the solid state relay is subject to correct installation, maintenance and use conforming to its intended regu-
lations and standards, to the supplier's instructions and to accepted rules of art.
Attention ! les relais à semi-conducteurs ne procurent pas d'isolation galvanique entre le réseau et la charge. Ils doivent être
utilisés associés à un disjoncteur avec propriété de sectionnement ou similaire, afin d'assurer un sectionnement fiable en amont
de la ligne dans l'hypothèse d'une défaillance et pour tous les cas où le relais doit être isolé du réseau (maintenance; non
utilisation sur une longue durée...).
Sous réserve d'installation, d'entretien et d'utilisation conformes à sa destination, à la réglementation, aux normes en vigueur,
aux instructions du constructeur et aux règles de l'art.
Protection /
Protection :
To protect a SSR against a short-circuit of the load , use a fuse with a I 2 t value = 1/2 I 2 t value specified page 2.
−>
A test has been made with FERRAZ SCHAWMUT fuses .
It is possible to protect SSR by MCB ( miniature circuit breaker) by using a SSR with high I 2 t value (5000A 2 s minimum).
See our application note about coordination of protection type "1" or type "2" according EN60947-4-1.
La protection d'un relais statique contre les court-circuits de la charge peut être faite par fusibles rapides avec des I 2 t = 1/2 I 2 t du relais.
->
Un test en laboratoire a été effectué sur les fusibles de marque FERRAZ SCHAWMUT.
Une protection par MCB ( disjoncteurs modulaires miniatures) est aussi possible en utilisant des relais avec I 2 t >5000A 2 s.
Voir notre note application concernant la coordination de protection type "1" ou type "2"
EMC /
CEM :
−>
Immunity: For the products, we give in our data-sheets immunity level according to the main standards: IEC/EN61000-4-4 &
IEC/EN61000-4-5. But we are also in conformity with other standards IEC/EN61000-4-2, IEC/EN61000-4-6,... in compliance with
IEC/EN60947-4-3.
Emission: celduc ® relais SSRs are mainly designed in compliance with standards for class A equipment (Industry).
−>
Use of the products in domestic environments may cause radio interference. In that case the user may be required to employ
additionnal devices to reduce EMC noise. SSRs are complex devices that must be interconnected with other equipment (loads, ca-
bles, etc.) to form a system. Because the other equipment or the interconnections may not be under the control of celduc ® relais, it
shall be the responsability of the system integrator to ensure that systems containing SSRs comply with the requirement of any rules
and regulations applicable at the system level.
Consult celduc ® relais for advices. Pre-testing can be performed in our laboratory.
->
Immunité : Nous spécifions dans nos notices le niveau d'immunité de nos produits selon les normes essentielles pour ce type de pro-
duit, c'est à dire IEC/ EN61000-4-4 & IEC/ EN61000-4-5. Mais nous respectons aussi les autres normes CEM IEC/ EN61000-4-2 ; IEC/
EN61000-4-6; .... en conformité avec la norme IEC60947-4-3.
−>
Emission : Nos relais statiques sont principalement conçus et conformes pour la classe d'appareils A (Industrie).
L'utilisation du produit dans des environnements domestiques peut amener l'utilisateur à employer des moyens d'atténuation supplé-
mentaires. En effet, les relais statiques sont des dispositifs complexes qui doivent être interconnectés avec d'autres materiels (charges, ca-
bles, etc) pour former un système. Etant donné que les autres materiels ou interconnexions ne sont pas de la responsabilité de celduc ® re-
lais, il est de la responsabilité du réalisateur du système de s'assurer que les systèmes contenant des relais statiques satisfont aux prescrip-
tions de toutes les règles et règlements applicables au niveau des systèmes.
Consulter celduc ® relais qui peut vous conseiller ou réaliser des essais dans son laboratoire sur votre application.
Fax +33 (0) 4 77 53 85 51
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21
fig 3 : Overload currents /
r
e
l
5, Rue Ampère BP30004
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Courants de surcharges
®
a
i
s
42290 SORBIERS - FRANCE
Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19
S/MON/SF541310/D/07/04/2020
page 3/3 F/GB
www.celduc.com

Publicité

loading