PROPANE CONVERSION KIT
#LCK-NK48TL-P30
For use with #NDK-48-TL
Direct Vent Gas Fireplace
___________________________________________________________________________________________________________
This fireplace is certified under U.S. and Canadian standards ANSI Z21.88-2019/CSA 2.33-2019, CSA 2.17- 2017
THE CONVERSION SHALL BE CARRIED OUT BY A
MANUFACTURER'S AUTHORIZED REPRESENTATIVE,
IN ACCORDANCE WITH THE REQUIREMENTS OF THE
MANUFACTURER, PROVINCIAL OR TERRITORIAL
AUTHORITIES HAVING JURISDICTION AND IN
ACCORDANCE WITH THE REQUIREMENTS OF THE
CAN/CGA-B149.1
INSTALLATION CODES.
CETTE CONVERSION DE GAZ DOIT ÊTRE EFFECTUÉE
PAR UN REPRÉSENTANT AUTORISÉ DU FABRICANT,
CONFORMÉMENT AUX EXIGENCES DU FABRICANT
ET
DES
AUTORITÉS
TERRITORIALES AYANT JURIDICTION, ET
EXIGENCES DES CODES D'INSTALLATION CAN/CGA-
B149.1 OU CAN/ CGA-B149.2.
This conversion kit shall be installed by a qualified
service
agency
manufacturer's instructions and all applicable
codes and requirements of the authority having
jurisdiction. If the information in these instructions
is not followed exactly, a fire, explosion or
productions of carbon monoxide may result,
causing property damage, personal injury, or loss
of life. The qualified service agency is responsible
for proper installation of this kit. The installation is
not proper and complete until operation of the
converted appliance is checked as specified in the
manufacturer's instructions supplied with the kit.
Refer to appliance owner's manual or product data
plate for proper inlet and manifold pressure
adjustments and orifice sizing.
NDK-48-TL
Rev. 1 - July 2024
IMPORTANT
OR
CAN/CGA-B149.2
PROVINCIALES
WARNING
in
accordance
with
READ ALL STEPS BEFORE STARTING INSTALLATION.
LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE.
This gas conversion kit installation instructions must be
used in conjunction with the installation and operation
manual provided with the appliance. Please read the
appliance owner's manual completely before performing
OU
any procedures in these instructions. All warnings,
AUX
precautions, and instructions outlined in the manual
provided with the appliance will continue to apply to
these instructions.
Ce kit de conversion doit être installé par une agence
d'entretien qualifiée, selon les instructions du
the
fabricant et tous les codes et règlements applicables
de l'autorité ayant juridiction. Le non-respect de ces
instructions peut créer un incendie, une explosion ou
l'émission de monoxyde de carbone, et causer des
dommages matériels, des blessures ou des pertes de
vie. L'agence d'entretien qualifiée est responsable de
la qualité d'installation de ce kit. L'installation ne sera
conforme et complète qu'après avoir vérifié le bon
fonctionnement de l'appareil converti, tel que
spécifié dans les instructions du fabricant fournies
avec ce kit.
Voir le manuel d'instructions ou la plaque
signalétique de l'appareil, pour les réglages de
pressions d'entrée et du manifold, et les
d'orifices (injecteurs) des brûleurs et de la veilleuse.
1
P.O. BOX 557 204 INDUSTRIAL PARK DRIVE
LAKEFIELD, MINNESOTA USA 56150-0577
AVERTISSEMENT
PFS Report Number: 24-299
Starting serial #24 N48TL00001 36
tailles

Publicité

loading

Sommaire des Matières pour Kozy Heat Fireplaces LCK-NK48TL-P30

  • Page 1 PROPANE CONVERSION KIT #LCK-NK48TL-P30 For use with #NDK-48-TL Direct Vent Gas Fireplace P.O. BOX 557 204 INDUSTRIAL PARK DRIVE LAKEFIELD, MINNESOTA USA 56150-0577 ___________________________________________________________________________________________________________ This fireplace is certified under U.S. and Canadian standards ANSI Z21.88-2019/CSA 2.33-2019, CSA 2.17- 2017 IMPORTANT THE CONVERSION SHALL BE CARRIED OUT BY A MANUFACTURER’S AUTHORIZED REPRESENTATIVE,...
  • Page 2 NDK-48-TL PFS Report Number: 24-299 Rev. 1 - July 2024 Starting serial #24 N48TL00001 36...
  • Page 3 Conversion Kit Components B. Replace Burner Orifices • (1) Gas Conversion Label 1. Remove the existing orifice caps. • (1) 30% Turndown Stepper Motor* 2. Replace with the orifice caps included with this kit. Tighten • (1) Gas Label caps securely. The sizes are stamped on the orifices. •...
  • Page 4 D. Convert Gas Control Valve F. Test Inlet Pressure It is easier to convert the gas control valve before placing the IMPORTANT: For a proper pressure reading, apply the gas gas fireplace insert into an existing fireplace. supply pressure tests with all other gas appliances on or at full capacity in the household.
  • Page 5 H. Verify Operation 1. Light the pilot. Visually check the pilot flame to verify Table 5, Input Ratings flame envelopes the top of the flame sensor and ex- tends far enough onto the burner for proper ignition. Fuel Minimum Maximum 2.
  • Page 6 B. Remplacer les orifices des brûleurs Composants du kit de conversion • (1) Étiquette de conversion de gaz 1. Retirez les orifices existants des brûleurs. • 2. Remplacez-les par les orifices fournis avec ce kit. Serrez (1) Moteur pas-à-pas (marge de réglage 30%)* bien les orifices.
  • Page 7 D. Convertir la valve de contrôle de gaz F. Tester la pression à l'entrée Il est plus facile de convertir la valve de contrôle de gaz IMPORTANT: Pour des mesures de pression adéquates, faire avant d’insérer en place le foyer à gaz. les tests de pression d'alimentation de gaz avec tous les appareils à...
  • Page 8 H. Vérifier le fonctionnement Tableau 5, Puissances de chauffage nominales 1. Allumez la veilleuse. Vérifiez visuellement que les flammes de la veilleuse enveloppent le haut du Combustible Minimum Maximum détecteur de flamme et se prolongent sur le brûleur assez loin pour assurer un allumage adéquat. Propane 40 000 Btu/h 51 000 Btu/h...