CP5.241-S2 Installation Manual
EN
Product Description
The CP5.241-S2 is a DIN-rail mountable single-phase-input power supply, which provides a floating,
stabilized and galvanically separated SELV/PELV output voltage.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring and measurement equipment or the like. Do not use this
device in equipment where malfunction may cause severe personal injury or threaten human life.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom and the
output terminals on the top of the device. Other mounting orientations require a reduction in output
current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost allowed.
The enclosure of the device provides a degree of protection of IP20.
The isolation of the device is designed to withstand impulse voltages of overvoltage category III
according to IEC 60664-1.
The device is designed as "Class of Protection I" equipment according to IEC 61140.
Do not use without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN-, TT- and IT mains networks. The voltage between the L
or N terminal and the PE terminal must not exceed 300Vac continuously.
The device can also be powered from batteries or similar DC sources. The voltage between the input
terminals and the PE terminal must not exceed 180Vdc continuously.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 6000m (19685ft). See additional requirements in the product
datasheet for use above 2000m (6560ft).
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive and capacitive loads. If capacitors with a capacitance >0.4F are
connected, the unit might charge the capacitor in an intermitted mode (Hiccup behavior).
Do not apply return voltages from the load to the output higher than 35V.
The output voltage can be adjusted with a small flat-blade screwdriver on the front.
The green DC-OK LED reports an output voltage above 90% of the adjusted voltage of a running device.
The DC-OK relay monitors the output voltage and the contact is closed when the DC-OK LED is on. Contact
ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically after cooling off.
At heavy overloads (when output voltage falls below 13V), the device delivers continuous output
current for 1s. After this, the output is switched off for approx. 9s before a new start attempt is
automatically performed. This cycle is repeated as long as the overload exists.
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to
exceed 40°C. The output voltage shall be adjusted to the same value (±100mV) with the same load
conditions on all devices, or the devices can be left with the factory settings. Energize all units at the
same time. It might be necessary to cycle the input power (turn-off for at least five seconds), if the
output was in overload or short circuit. If more than three devices are connected in parallel, a diode,
fuse or circuit breaker with a rating of 10A is required on each output.
Same devices can be connected in series for higher output voltages. It is allowed to connect as many
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output
shuts down and performs three restart attempts. If the failure continues, the output shuts down. Cycle
input power to reset.
Technical data
All values are typical figures specified at 230Vac 50Hz input voltage, 24V
5A output load, 25°C ambient temperature and after a 5 minutes run-in
time unless otherwise noted.
Output voltage
DC 24V
Adjustment range
24 – 28Vdc
Output current
6.0 – 5.1A
5.0 – 4.3A
3.8 – 3.2A
Derate linearly between +45°C and +70°C
Input voltage AC
AC 100 - 240V
Mains frequency
50 – 60Hz
Input current AC
1.09 / 0.6A
Power factor
0.98 / 0.91
Input voltage DC
DC 110 - 150V
Input current DC
1.21A
Input inrush current
4 / 4A pk
Efficiency
93.6 / 94.3%
Power losses
8.2 / 7.3W
Hold-up time
35 / 35ms
Temperature range
-25 to +70°C
Max. wire size (litz wire)
2.5mm²
Max. wire size with ferrules 1.5mm²
Wire size AWG
AWG 24-12
Maximum wire diameter
2.3mm
Wire stripping length
10mm / 0.4inch
Max. wire size (litz wire)
1.5mm²
Wire size AWG
AWG 24-16
Max. wire diameter
1.6 mm
Wire stripping length
7mm / 0.28inch
Size (wxhxd)
32x124x102mm
Weight
440g / 0.97lb
Functional diagram
L
Input Fuse
Input Filter
PFC
N
Input Rectifier
Converter
Inrush Current
Limiter
Temper-
Output
Output
ature
Over-
Power
Shut-
Voltage
Manager
down
Protection
Output characteristic
Output voltage
28V
24V
12V
A: continuous current
B: intermitted current
0V
0A
1A
2A
3A
4A
Temperature range
Allowed output current at 24V
6A
5A
3.75A
A: continuous
B: short term (max. 60s)
0A
-25
0
+25
Nominal
Factory setting 24.1V
Below +45°C ambient
At +60°C ambient
At +70°C ambient
-15% / +10%
±6%
At 120 / 230Vac
At 120 / 230Vac
±20%
At 110Vdc
At 40°C, 120 / 230Vac
At 120 / 230Vac
At 120 / 230Vac
At 120 / 230Vac
Power terminals
Power terminals
Power terminals
Power terminals
Power terminals
DC-OK terminals
DC-OK terminals
DC-OK terminals
DC-OK terminals
Without DIN-rail
Voltage
V
Regulator
OUT
+
+
Power
Output
Converter
Filter
-
-
DC-OK
LED
13
DC-ok
DC-OK
Relay
14
Contact
Adjustment range
A
B
5A
6A
7A
8A
Output current
+45
+60
+70°C
Ambient temperature