L1 OUT
Alarm LED
Power LED
LCD Display
Down Button
Up Button
Mode Button
Auxiliary Terminals
Main Terminals
L1-IN
L1 IN
Technical Support Call 1-800-231-3345
All surge protection devices require a good ground
connection for effective operation
120/240 Single Phase, 60 Amp Double Pole
Capacity Relays (handles loads up to 60 Amps)
96424
PRODUC T CODE
L2 OUT
RSH VRM60A
RSH-MS60A
U 240
L2-IN
Surge Protector
L2 IN
Input
I N S T A L L A T I O N I N S T R U C T I O N S
Type 1 SPD
Open-type
5ME8
Operating Control
RSH-50
RSH VRM60A
Installation Instructions
1.
Device must be installed in an enclosure suitable for the application
and environment for which it is being used. Connected load shall not
exceed 60 amps.
2.
Confirm power is OFF prior to performing the installation.
3.
Use the appropriate wire size and type based on the connected load
and torque to the specified ratings.
4.
Connect input and output connections, replace finger guard covers
and then restore power.
5.
Confirm power LED is illuminated and proceed to programming
functions.
6.
Optional mounting feet included to secure enclosure to wall or
structure.
Programming Instructions
Start Up: At power up, load will remain disconnected for 2 minutes. This
delay is adjustable. To view event logs, press UP button.
- Over voltage events,
- Under voltage events,
To enter program mode - Press and hold MODE button for 2 seconds
Mode
- Power on delay. Use the UP & DOWN buttons to adjust the delay
time between 1 and 10 minutes before the load is restored from the discon-
nect switch or a power outage. Default setting: 2 minutes.
Mode
- Utility over-voltage set point. Use the UP & DOWN buttons to
set the desired over-voltage cut off point between 85–300 vac Press MODE
button to advance to next setting.
Mode
- Utility under-voltage set point. Use the UP & DOWN buttons
to set the desired under-voltage cut off point between 85–300 vac. Press
MODE button to advance to next setting.
Mode
- Over/under delay. Use the UP & DOWN buttons to
adjust the delay time between .5 and 60 seconds before the load is
disconnected when an under or over voltage condition is present. Press
MODE button to advance to next setting.
Mode
- Load restore delay. Use the UP & DOWN buttons to adjust the
delay time between 1 and 600 seconds before the load is restored after
normal power levels have returned.
Mode
- Event-log clear. To retain stored events, set to 1. To clear ALL
stored events, set to . Press and hold the MODE button for 2 seconds to
save changes and exit.
Diagram
Main Terminals
CU7 Copper Conductors Only
10-14 AWG 35 IN. LBS.
8 AWG 40 IN. LBS.
4-6 AWG 45 IN. LBS.
2-3 AWG 50 IN. LBS
Auxiliary Terminals
CU7 Copper Conductors Only
12–16 AWG 20 IN. LBS.
5NT1
- Outages