ENCOUNTERED PROBLEMS
• Wrong cable connections,
• Open or short circuit of Inputs or outputs,
• Wrong programming by Loop Manager causes to the faulties or wrong operation.
TECHNICAL SPECIFICATION
Damper Operating Voltage
Cable Type
• Automatic fuse shall be used for 230V AC mains connection.
• The fuse value shall be determined by reference to the maximum current value of the damper to be used and shall not exceed 6 amps.
TECHNICAL SPECIFICATION FOR WITH SHORT CIRCUIT MODEL
Case of Short Circuit Rated Current (ILmax)
BOX CONTENTS
Product box is included with below items.
ML-1356.X / ML-1357.X / 1358.X
User Manual
For ML-1356.X
For ML-1357.X
For ML-1358.X
MODELS
Product Description
ML-1356
ML-1356.SCI
ML-1357
ML-1357.SCI
ML-1358
ML-1358.SCI
KK-631.032 Rev.No:5 04.04.23 ML-1356.X / ML-1357.X / 1358.X Kullanma Kılavuzu / User Manual / Manuel utilisateur / Руководство по эксплуатации
Operating Voltage
ML-1356 / ML-1356.SCI
ML-1357 / ML-1357.SCI
ML-1358 / ML-1358.SCI
Damper Control Output Capacity
Operating, Storage Temp.
Relative Humidity
Height/Width/Depth
Comm. Protocol
Loop & Position
Module & Damper
Supply Voltage
Maximum Supply Voltage (Vmax)
Nominal Supply Voltage (Vnom)
Minimum Supply Voltage (Vmin)
Maximum Switching Current (ISmax)
Maximum Operating Current (ICmax)
Maximum Contact Resistance (ZCmax)
Isolating Voltage (VSOmin - VSOmax)
Reconnect Voltage (VSCmin - VSCmax)
Product Description
Maxlogic Intelligent Addressable System Smoke Damper Module
1 pcs.
Resistor: 0 Ω (2 pcs) + 10k Ω (4 pcs) + 4.7k Ω (6 pcs) / Jumper: 6 pcs
Resistor: 0 Ω (2 pcs) + 10k Ω (4 pcs) + 4.7k Ω (6 pcs) / Jumper: 6 pcs
Resistor: 0 Ω (2 pcs) + 10k Ω (4 pcs) + 4.7k Ω (4 pcs) + 220k Ω (2 pcs) / Jumper: 6 pcs
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 24V DC
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 24V DC, Short Circuit Isolator
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 24V AC
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 24V AC, Short Circuit Isolator
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 220V AC
Maxlogic Intelligent Addressable System Smoke Damper Module, 1 Output, 220V AC, Short Circuit Isolator
18-33V DC (Loop Powered)
24V DC (19V-30V DC)
24V AC (+%10, -%15)
230V AC (+%10, -%15)
5A
(-30°C) - (+60°C)
%95 (without condensation at 40°C)
108mm / 158mm / 49mm
VIP / ~1000 baud
1x2x0,8+0,8JH(st)H
Monitoring
1x2x1,0+1,0JH(st)H
1x2x1,5+1,5JH(st)H
Power Cable of Damper: 3x0,75 mm² (L/N/PE)
Spring-Return Actuator: 2x0,75 mm² (Halogen Free)
Non-Spring-Return Actuator: 3x0,75 mm² (Halogen Free)
Elektromagnetic System: 3x0,75 mm² (Halogen Free)
33V
26V
18V
1A
1A
<45 mA
500 mΩ
8V - 13V
8V - 13V
5/15