Installation Instructions:
Caution: Circuit may be energized. 100-240 VAC 50/60 Hz
1) Verify circuit with a voltmeter or inductive AC power probe that AC power has been turned OFF. Recommend securing
circuit power OFF via Lock-Out/Tag-Out methods prior to installation, service, or replacement of unit.
2) Loosen the 2 enclosure/cover retaining screws and rotate the power supply integrated cover plate to allow internal access
of the 4" L x 4" W x 2-1/8" D electrical enclosure box.
3) Connect the 4" L x 4" W x 2-1/8" D electrical enclosure box to conduit (conductor/cable clamps are NOT provided) and
securely fasten the enclosure with suitable fasteners to a frame or support member. Two holes are accessible in the
bottom of the enclosure with the supply installed on the standoffs. A minimum of (2) screws should be inserted through
the enclosure holes and secured into a wooden or steel stud, frame support, or other supporting surface. Suitable
fasteners (wood screws, sheet metal screws, or expansion fasteners are not provided with this product).
Note: Do not remove supply from the enclosure.
4) Connect the P6000-HW6 power supply to the AC service conductors as outlined below in the diagrams.
The internal (Line & Neutral) conductor terminations/connections, shall be implemented using UL approved screw
terminals, wire nuts, insulated crimp splices, or soldered using hook & loop method with the solder joint(s) post insulated
or as specified within the National Electrical Code (NEC) and/or superseding relevant local specified code(s).
5) Connect frame/safety ground from AC service as oulined above.
6) Verify continuity between the enclosure and the frame/safety ground supply line.
7) Form conductor leads as required to allow unimpeded installation of the cover plate (with integrated terminal block) to
the electrical box enclosure and secure the cover with the 2 cover screws.
8) Restore AC power and measure the low voltage output with a DC voltmeter to verify output to be ~7.6 VDC.
9) Install M4.0 or #8 ring or spade crimp terminals (not provided) to the product leads for attachment to the low voltage
output terminals as labeled.
Note: For remote lengths of < 40', recommend utilizing 18AWG, CMP, CMR, CMX or other UL performance category
type cables as specified in the NEC for overhead, behind walls, vertical shafts, and/or plenum installations. Remote
installation to the final product connector/cable should be implemented using a Mini-junction box, insulated connectors/
crimp splices/screw terminals, or soldered using hook and loop method with the solder joint(s) post insulated with heat
shrink or electrical tape.
10) Ground Jumper is required for sensor circuit noise reduction and should not be removed.
FV522