5.3
Remarques UL
AVERTISSEMENT : risque d'explosion en cas d'utilisation en atmosphères explosibles
Assurez-vous que les avis suivants et que les instructions sont respectés !
U = 42 - 57 V DC
P = max. 60 W
Amb. Temp.: -40°C < T < 75°C
IND. CONT. EQ., ALSO
Class I, Zone 2, AEx nA IIC T4, Ex nA IIC Gc X T4
LISTED IND. CONT.
Class I, Division 2, Groups A, B, C and D
EQ. FOR HAZ. LOC.
E366272
 
INDUSTRIAL CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS
A)
This equipment must be mounted in an enclosure certified for use in Class I, Zone 2 minimum
and rated IP54 minimum in accordance with IEC 60529 when used in Class I, Zone 2
environment.
B)
Device shall only be used in an area of not more than pollution degree 2.
C)
If the equipment is used in a manner not specified, the protection provided by the equipment
may be impaired.
D)
Minimum temperature rating of the cables to be connected to the field wiring terminals: 80°C
E)
The external circuits connected to the terminal of the device must be supplied from SELV/PELV.
F)
The device has to be built in the final safety enclosure, which has adequate rigidity according
to UL 61010-1, UL 61010-2-201 and meets the requirements with respect to spread of fire.
G)
Use copper conductors only.
 
6
Transport et déballage
Contrôler si la livraison n'a pas été endommagée pen-
dant le transport.
En cas d'endommagements lors du transport, il faut
faire la réclamation immédiatement. Informez immédia-
tement Phoenix Contact ou votre fournisseur, ainsi que
l'entreprise de transport.
Lisez attentivement les instructions d'installation.
Conservez les instructions d'installation.
Conserver l'emballage pour un éventuel transport ulté-
rieur.
107964_fr_06
a
PP-RJ-...-F
PHOENIX CONTACT
11 / 18