DXTH
TRANSMETTEUR / COMMUTATEUR DOUBLE POUR TEMPÉRA-
TURE ET L'HUMIDITÉ RELATIVE POUR LE CONDUITS
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
3
Modbus parity mode
4
Device type
5
HW version
6
FW version
7
Operating mode
8
Output overwrite
9-10
11
Temperature range
12
Relative humidity range
Minimum custom
13
temperature range
Maximum custom
14
temperature range
Minimum custom relative
15
humidity range
Maximum custom relative
16
humidity range
Temperature setpoint
17
relay 1
Relative humidity setpoint
18
relay 2
19-20
Analogue output 1
21
overwrite value for
temperature, Ao1
Analogue output 2
22
overwrite value for relative
humidity, Ao2
23-30
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-DXTH-FR-000 - 12 / 10 / 15
Data type
Description
unsigned int.
Modbus device address
unsigned int.
Modbus communication baud rate
unsigned int.
Parity check mode
unsigned int.
Device type (Read only)
unsigned int.
Hardware version of the device (Read only)
unsigned int.
Firmware version of the device (Read only)
Enables Modbus control and disables the jumpers and
unsigned int.
trimmers
Enables the direct control over the outputs. Always settable.
unsigned int.
Active only if holding register 7 is set to 1.
Reserved, returns 0
Selects the temperature working range. Always settable.
signed int.
Active only if holding register 7 is set to 1.
Selects the relative humidity working range. Always
signed int.
settable. Active only if holding register 7 is set to 1.
Minimum value of the custom temperature range. Always
signed int.
settable. Active only if holding register 7 is set to 1 and
register 11 is set to 5.
Maximum value of the custom temperature range. Always
signed int.
settable. Active only if holding register 7 is set to 1 and
register 11 is set to 5.
Minimum value of the custom relative humidity range.
signed int.
Always settable. Active only if holding register 7 is set to 1
and register 12 is set to 5.
Maximum value of the custom relative humidity range.
signed int.
Always settable. Active only if holding register 7 is set to 1
and register 12 is set to 5.
Selects the setpoint for the temperature relay switching.
signed int.
Always settable. Active only if holding register 7 is set to 1.
Selects the setpoint for the relative humidity relay
signed int.
switching. Always settable. Active only if holding register 7
is set to 1.
Reserved, returns 0
Overwrite value for the temperature analogue output.
signed int.
Always settable. Active only if holding registers 7 and 8
are set to 1.
Overwrite value for the relative humidity analogue
signed int.
output. Always settable. Active only if holding registers
7 and 8 are set to 1.
Reserved, returns 0
Retour à la Table des matières
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
Data
Default
Values
1—247
1
1 =
2 =
1—4
2
3 =
4 =
0 =
0—2
1
1 =
2 =
DXTHX=1036
XXXX
0 x 0110 =
XXXX
0x0120 =
0 =
0—1
0
1 =
0 =
0—1
0
1 =
1 =
2 =
1—5
1
3 =
4 =
5 =
1 =
2 =
1—5
1
3 =
4 =
5 =
0—Max
0
100 =
Min—500
500
500 =
0—Max
0
200 =
Min—1.000
1.000
1.000 =
0—500
250
250 =
0—1.000
500
500 =
0 =
0—1.000
0
1.000 =
0 =
0—1.000
0
1.000 =
9.600
19.200
38.400
57.600
8N1
8E1
8O1
HW version 1.10
FW version 1.20
Standalone mode
Modbus mode
Disabled
Enabled
0—30 °C
10—40 °C
20—50 °C
0—50 °C
Custom
20—90 % rH
0—60 % rH
0—80 % rH
0—100 % rH
Custom
10,0 °C
50,0 °C
20,0 % rH
100,0 % rH
25,0 °C
50,0 % rH
0 %
100 %
0 %
100 %
10 - 11