Télécharger Imprimer la page

Johnson SUIT Serie Guide D'utilisation page 37

Publicité

Les langues disponibles

Les langues disponibles

5.1 Air-conditioning unit wiring
Capacity
Power Supply
(kW)
Single-phase
10
220V-240V~50Hz
Three-phase
380V~50Hz/60Hz
14/16
Three-phase
380V~50Hz/60Hz
22
If needed, the user can purchase a centralized controller, as shown in the dashed box. For the specific method of
installation, please contact your local supplier.
Power supply
Air-conditioning unit
Centralized
controller
CCM
Indoor unit
P Q
Three-core
shielded cable
to centralized
Three-core
controller
shielded
cable
P
Q E
X
Y
E
Air-conditioning unit
Fig. 5-2 Electrical Wiring of Single-phase Air-conditioning Units
NOTE
When the signal line uses a two-core shielded cable, the shielding net shall be connected to "E" of the
terminal block. When the signal line uses a three-core shielded cable, the shielding net shall be connected
to the ground.
Never connect the power line (strong current) to the terminal block of the signal line (weak current).
Otherwise, the power board will be burnt out.
5. Electrical Wiring
Table 5-1 Air-conditioning Unit Wiring
Power Line
(mm²)
3×6
5×2.5
5×6
Power supply
Switch / power supply
Power line of
air-conditioning unit
Indoor unit
Fig. 5-1 Wiring and Control
L N
E
Y/G
Single-phase power supply
220V-50Hz/60Hz
L N
Y/G
Single-phase power supply
220V-50Hz/60Hz
Breaker/
Signal Wire of Indoor/Air-conditioning Units (mm)
Fuse (A)
40/35
three-core shielded cable 3×1.0 (two-core shielded cable 2×1.0)
three-core shielded cable 3×1.0 (two-core shielded cable 2×1.0)
25/20
35/30
three-core shielded cable 3×1.0 (two-core shielded cable 2×1.0)
Switch / power supply
Power line of indoor unit
Indoor unit
N
L1 L2 L3
Three-phase power supply 380V3N-50Hz/60Hz
Fig. 5-3 Electrical Wiring of Three-phase Air-conditioning Units
12
(Signal Wire of Weak Current)
Junction box
Indoor unit
Indoor unit
P
Q E
Single-phase power supply
220V-50Hz/60Hz
Three-core shielded
cable to centralized
Three-core
shielded
controller
cable
E
P
Q
Y/G
Air-conditioning unit
L
N
Y/G
X
Y
E
V.1

Publicité

loading

Ce manuel est également adapté pour:

Suit100cenSuit160cenySuit140cenySuit224ceny