Converter configuration
AKO-80039
Maximum of one converter per web server
s Š ‡ ? AKO-80039 converter included comes pre-installed out of the box to operate without needing additional
configuration. However, if the software does not detect any device, check the converter indicators:
The red and green indicators are flashing: Standard operation
Ÿ
Only the red indicator is flashing: Check the installation between the devices and the converter and
Ÿ
their configuration.
No indicator is flashing: Check the configuration on the AKO-5014 web server.
Ÿ
Configuration
-Access the administration / general configuration menu
-Select the device and press "Edit".
-Check whether there are other ports available. If
so, select another port, press "Accept" and
repeat the search for devices checking that both
indicators are flashing.
AKO-80080
Maximum of 2 converters per web server
The AKO-80080 converter (not included) requires a specific configuration on the AKO-5014 web server.
Configuration
-Access the administration / general configuration menu
-Press "New".
-Name the installation.
-Change the installation type to "Ethernet" and
enter the IP address assigned to the converter
(see the converter manual). The "RTU mode"
must be disabled and the "Read Timeout"
must be 500.
-Press "Accept"
13
5014H001 Ed.03